26
5. The circulating air blower will energize after the
temperature fan switch closes.
6. The furnace runs until the call for heat is satisfied.
7. The circulating air blower will de-energize when the
temperature fan switch opens.
Gas Gun Furnaces (M1B Models)
1. On a call for heat, the furnace control begins an ignition
sequence which lasts approximately 45 seconds.
2. After this sequence, the control module tests to see if
flame is sensed. If it has, the furnace continues to heat
until the thermostat is satisfied.
3. If the burner has not lit, the ignition sequence is repeated
a maximum of two more times. If flame is not sensed
after three attempts, the control enters Lockout and
no further attempts to light the burner will occur. If
Lockout occurs, contact a qualified service technician
for assistance.
4. When call for heat is satisfied, the thermostat contacts
open and the gas valve shuts off gas flow.
WaRnInG:
should overheating occur, or the gas supply fails
to shut off, shut off the manual gas valve to the
furnace before shutting off the electrical supply.
aVERtIssEMEnt:
En case de température excessive, ou sail est
impossible de cooper l’alimentation en gaz,
fermer le robinet manuel d’alimentation en gaz
du générateur d’sir chaud avant de cooper
l’alimentation électrique.
FuRnacE contRols & FunctIons
Furnace on / off switch:
This switch turns electrical
power to the furnace on and off. The switch must be set
in the ON position for the furnace to operate. If blower
operation is not desired, the furnace On-Off switch may
be set in the Off position to cut the electrical power to the
furnace. See
Limit Control:
This furnace is protected by two high
temperature safety limit switches. The auxiliary (upper)
limit switch and the high temperature (lower) limit switch
are automatic reset types. If either limit trips, the burner
will shut off. If either limit switch trips off again soon after
resetting, set the furnace furnace On-Off switch to the
Off position and call your authorized serviceman. See
Blower off Delay:
When the blower fan operates under
cooling mode, there is a 40 second delay after the call
for cooling (from the thermostat) is satisfied before the
blower turns off.
Gas Valve:
The gas valves for the gas furnaces are a
100% shut-off type and will fail safe, if for some reason the
gas is turned off. The valve is a “slow-open” for M1M and
M1B models which means it opens to a low-fire position,
and after a few seconds, “steps-open” to high-fire.
oil Burner Primary control:
The primary control for oil
gun furnaces starts the burner, monitors a safe operating
cycle, and shuts the burner off at the end of a heating
cycle. The control uses a light sensing transducer to
determine if fuel ignition has been successfully attained.
If ignition is not attained by the end of the safety ignition
timing period, the control shuts the burner off and enters
“lock-out.” See
.
summer cooling - (B, c, & D series):
Your furnace is
A/C ready, equipped with A/C relay and transformer. The
unit is equipped to use a 4-wire thermostat. When using
a 5-wire thermostat, RC and RH should be jumped (see
instructions included with thermostat).
Figure 33
Furnace
On-Off
Switch
Oil
Pump
Fan
Control
Lower
Limit
Switch
Upper
Limit
Switch
Oil
Burner
Control
Figure 33. Furnace controls - oil Furnace