Modbus Master to BACnet Server gateway

 

Order Code:

 INBACMBM***0000 

** stands for the Intesis gateway capacity and varies depending on the specific gateway acquired 

Installation Sheet rev.1.8 

HMS Industrial Networks S.L.U ©

 

SAFETY INSTRUCTIONS 

     

!

     

WARNING 

Follow  carefully  this  safety  and  installation  instructions. 
Improper work may lead to serious harmful for your health 
and also may damage seriously the Intesis gateway and/or 
any other equipment connected to it. 

 

The  Intesis  gateway  must  be  installed  by  accredited  electrician  or 
similar  technical  personnel,  following  all  the  safety  instructions  given 
here  and  in  accordance  always  with  the  country  legislation  for 
installation of electric equipment. 

 

The Intesis gateway cannot be installed outdoors or exposed to direct 
solar radiation, water, high relative humidity or dust. 

 

The  Intesis  gateway  must  only  be  installed  in  a  restricted  access 
location.  

 

In  case  of  wall  mount,  fix  firmly  the  Intesis  device  on  a  not  vibrating 
surface following the instructions next. 

 

In case of DIN rail mount fix the Intesis device properly to the DIN rail 
following the instructions below.  

 

Mounting  on  DIN  rail  inside  a  metallic  cabinet  properly  connected  to 
earth is recommended. 

 

Disconnect  always  power  of  any  wires  before  manipulating  and 
connecting them to the Intesis gateway. 

 

A power supply with an NEC Class 2 or Limited Power Source (LPS) 
and SELV rated is to be used.  

 

Respect  always  the  expected  polarity  of  power  and  communication 
cables when connecting them to the Intesis gateway.  

 

Supply  always  a  correct  voltage  to  power  the  Intesis  gateway,  see 
details  of  voltage  range  admitted  by  the  device  in  the  technical 
characteristics below.  

 

CAUTION: Risk of Explosion if Battery is replaced by an Incorrect Type. 
Dispose  of  Used  Batteries  according  to  the  instructions.  Battery 
replacement shall be done by an authorized installer. 

 

CAUTION:  The  device  is  to  be  connected  only  to  networks  without 
routing to the outside plant, all communication ports are considered for 
indoor only and can be connected SELV circuits only. 

 

This  device  was  designed  for  installation  in  an  enclosure.  To  avoid 
electrostatic  discharge  to  the  unit  in  environments  with  static  levels 
above 4 kV, precautions should be taken when the device is mounted 
outside  an  enclosure.  When  working  in  an  enclosure  (ex.  making 
adjustments,  setting  switches  etc.)  typical  anti-static  precautions 
should be observed before touching the unit. 

 

Safety instructions in other languages can be found at: 

https://intesis.com/docs/manuals/v6-safety 

 

 

INSTALLATION 

Follow instructions next to properly install the gateway. 

 
Disconnect  from  mains  the  power  supply  before  connecting  it  to  the 
Intesis gateway. 

 

Disconnect  power  of  any  bus  or  communication  cable  before 
connecting it to the Intesis device. 

 

Mount  the  Intesis  gateway  on  the  wall  or  DIN  rail  following  the 
instruction given below, respecting the safety instructions given above. 

 

Connect  a  NEC  Class  2  or  Limited  Power  Source  (LPS)  and  SELV 
rated  power  supply  to  the  Intesis  gateway,  respect  the  polarity  if  DC 
power or Line and Neutral if AC power. Apply always a voltage within 
the  range  admitted  by  the  Intesis  device  and  of  enough  power  (see 
technical characteristics). 

 

Circuit-breaker must  be  used  before  the  power  supply.  Rating  250V-
6A. 

 

Connect the communication cables to the Intesis gateway, see details 
on the user's manual. 

 

Power the Intesis device and the rest of devices connected to it. 

NOTE: 

The device cannot be installed in air-handling space.

 

Wall Mount 

1.  Separate  the  fixing  clips  in  the  bottom  of  the  box,  pushing 

them to the outside until hear the "click" which indicates that 
now the clips are in position for wall mount, see in the figure 
below. 

2.  Use  the  holes  of  the to fix  the  box  in the  wall  using screws. 

Use the template below for the wall wholes. 
 

 

 

 

 

 
 

 Clips in their original position       Clips in position for wall mount 

    (for DIN rail mount) 

 

DIN Rail Mount 

With the clips of the box in their original position, insert first the box 
in the upper edge of the DIN rail and later insert the box in the down 
part of the rail, using a small screwdriver and following the steps in 
the figure below.  

 

 

Press 

Press 

Press 

CONFIGURATION 

Use the 

Configuration Tool

 to configure the gateway. 

 

See instructions to download and install the latest version at:  

https://intesis.com/docs/software/intesis-maps-installer

 

 

Use  the  Ethernet  connection  or  the  Console  Port  (mini  USB  type  B 
connector included) for communication between the gateway and the 
configuration tool. See CONNECTIONS below and follow instructions 
of user’s manual for more details. 
 

Owner’s Record 

The serial number is located at the rear of the gateway. 
Record  this  information  in  the  space  provided  below. 
Refer  to  it  whenever  you  contact  upon  your  gateway 
dealer or support team regarding this product. 

Serial No.

                         