When
“Scaling [DPT 5.001]”
is selected,
Control_ Fan Speed
and
Status_ Fan Speed
communication objects
for this DPT will appear.
The next table shows the range of values that can be sent through the
Control_
object
and the value returned by the
Status_
object.
Important:
Read the documentation of your indoor unit to check how many fan speeds
are available.
4.4.5 Enable use of +/- object for Fan Speed
This parameter shows/hides the
Control_ Fan Speed +/-
communication object which lets
increase/decrease the indoor unit fan speed by using two different datapoint types.
o
If set to
“no”
the object will not be shown.
o
If set to
“yes”
the
Control_ Fan Speed +/-
object and a new parameter will appear.
Figure 4.16
Parameter detail
Fan Speed 1
Fan Speed 2
Fan Speed 3
Fan Speed 4
Control_
0% - 74%
75% - 100%
Status_
50%
100%
Control_
0% - 49%
50% - 82%
83% - 100%
Status_
33%
67%
100%
Control_
0% - 37%
38% - 62%
63% - 87%
88% - 100%
Status_
25%
50%
75%
100%