o
When
“Enumerated [DPT 5.010]”
is selected,
Control_ Vanes U-D
and
Status_ Vanes
U-D
communication objects
for this DPT will appear.
To choose a vanes position, values from
“
1
”
to
“4”
(or
“5”
when available)
can be sent
to the
Control_
object. Each value will correspond to the position (i.e. Value
“3”
=
Position 3).
The
Status_
object will always return the value for the vane position selected.
Important:
If a
“0”
value is sent to the Control_ object, the Position 1 will be
selected. If a value bigger than
“4”
(or
“5”
when available) is sent to the Control_
object, then the higher Position will be selected.
o
When
“Scaling [DPT 5.001]”
is selected,
Control_ Vane Up-Down
and
Status_ Vane
Up-Down
communication objects
for this DPT will appear.
The next table shows the range of values that can be sent through the
Control_
object
and the value returned by the
Status_
object.
Important:
Read the documentation of your indoor unit to check how many vane
positions are available.
4.5.5 Enable use of +/- object for Vanes U-D
This parameter shows/hides the
Control_ Vane Up-Down +/-
communication object which
lets change the indoor unit vane position by using two different datapoint types.
o
If set to
“no”
the object will not be shown.
o
If set to
“yes”
the
Control_ Vanes U-D +/-
object and a new parameter will appear.
Vanes Pos.1 Vanes Pos.2 Vanes Pos.3 Vanes Pos.4 Vanes Pos.5
Control_
0% - 37%
38% - 62% 63% - 87% 88% - 100%
Status_
25%
50%
75%
100%
Control_
0% - 29%
30% - 49% 50% - 69% 70% - 89% 90% - 100%
Status_
20%
40%
60%
80%
100%