4.8 Switch-Off Timeouts Configuration dialog
Figure 4.34
Default Switch-Off Timeouts Configuration dialog
All the parameters in this section are related with the timeout properties and
communication objects.
4.8.1 Enable use of Open Window / Switch off timeout function
This parameter shows/hides the
Control_ Switch Off Timeout
communication object which
lets Start/Stop a timeout to switch off the indoor unit.
o
If set to
“no”
the object will not be shown.
o
If set to
“yes”
the
Control_ Switch Off Timeout
object and new parameters will appear.
If a
“1”
value is sent to this object, and the indoor unit is already turned on, the switch-
off timeout will begin. If a
“0”
value is sent to this object, the switch-off timeout will
stop.
Figure 4.35
Parameter detail
➢
AC switch-off timeout (min)
This parameter lets select how much time (in minutes) to wait before switching off
the indoor unit.