Figure 4.38
Parameter detail
➢
Timeout to apply action (minutes)
This parameter lets choose how much time to wait (in minutes) before
executing the action specified in the next parameter (
“Action after
timeout elapsed”
).
➢
Action after timeout elapsed
When
Switch-Off
is selected, once the timeouthas elapsed, the indoor
unit will turn off.
When
Apply Preset Delta
is selected, once the timeout configured is
extinguished, a delta temperature will be applied (decreasing the
setpoint when in Heat mode, or increasing the setpoint when in Cool
mode). Also new parameters will appear.
➢
Temp delta decrease (HEAT) or increase (COOL) (ºC)
This parameter lets configure the delta temperature that will be
applied when the timeout is extinguished.
Important:
When there is occupancy again after the
application of a delta, the same delta will be applied inversely
as explained above.
➢
Disallow On/Off operation while not Occupied
If set to
“no”
, On/Off commands while the window is open will be accepted.
•
If a
“1”
value is sent to the
Control_ Occupancy
object the switch-off timeout
period will begin again.
•
If a
“0”
value is sent to
the
Control_ Occupancy
object, no action will be
performed.
If set to
“yes”
, On/Off commands while not occupied will be saved (but not applied).
These commands will be used in the next parameter if set to
“yes”
.