When
“On”
is selected, the binary input will send a telegram with a
“1”
value
after a bus recovery. Also a new parameter will appear (see below).
•
When
“Off”
is selected, the binary input will send a telegram with a
“0”
value
after a bus recovery. Also a new parameter will appear (see below).
Figure 4.43
Parameter detail
➢
Sending delay after a bus recovery (seconds)
This parameter lets configure a delay (in seconds) that will be applied after a
bus recovery and, after which, a telegram will be sent.
➢
Value on rising edge
This parameter lets
select the value that the Binary Input “x” will send on a rising
edge (contact activated).
•
When
“
On
”
is selected, the binary input will always send telegrams with a
“1”
value.
•
When
“
Off
”
is selected, the binary input will always send telegrams with a
“0”
value.
•
When
“Toggle (On/Off)”
is selected, the binary input will send a
“1”
value
after a
“0”
value and viceversa.
•
When
“No action”
is selected, the binary input will not perform any action.
➢
Value on falling edge
This parameter lets
select the value that the Binary Input “x” will send on a falling
edge (contact deactivated).
•
When
“On”
is selected, the binary input will always send telegrams with a
“1”
value.
•
When
“Off”
is selected, the binary input will always send telegrams with a
“0”
value.
•
When
“Toggle (On/Off)”
is selected, the binary input will send a
“1”
value
after a
“0”
value and viceversa.
•
When
“No action”
is selected, the binary input will not perform any action.
➢
Cyclical sending
This parameter lets enable/disable cyclical sending when a determined condition is
met.