Figure 4.46
Parameter detail
➢
Sending delay after a bus recovery (seconds)
This parameter lets configure a delay (in seconds) that will be applied after a
bus recovery and, after which, a telegram will be sent.
➢
Mode for short (long) operation
This parameter lets
select the value that the Binary Input “x” will send on a rising
edge (contact activated), for a short and a long operation.
•
When
“On
(increase)
”
is selected, the binary input will always send
telegrams with a
“1”
value for a short operation, and an
“increase step”
for
a long operation.
•
When
“Off
(decrease)
”
is selected, the binary input will always send
telegrams with a
“0”
value for a short operation, and an
“decrease step”
for
a long operation.
•
When
“Toggle
: On/Off (increase/decrease
)”
is selected:
o
For the short operation the binary input will send a
“1”
value after a
“0”
value and viceversa.
o
For the long operation the binary input will send an
“increase step”
after
a
“decrease step”
and viceversa.
Important:
Note that the first long operation in toggle depends on the last short
operation, meaning that after a
“1”
value will be sent a
“decrease step”
and after
a
“0”
value will be sent an
“increase step”
.
Important:
The time period between a short and a long operation is defined in the
parameter “Short/long operation limit (x100ms)”.
➢
Increasing step
This parameter lets select the increasing step value (in %) that will be sent for a long
operation.
➢
Decreasing step
This parameter lets select the decreasing step value (in %) that will be sent for a
long operation.