Figure 4.49
Parameter detail
➢
Send telegram after bus recovery
This parameter lets select if the Binary Input “x” will send a telegram, or not, after a
bus recovery and the type of telegram sent (if enabled).
•
When
“No action”
is selected, no telegram will be sent after a bus recovery.
•
When
“Fixed value”
is selected, the binary input will send a telegram with
the same value configured in the “Value on rising edge” parameter.
Also a
new parameter will appear (see below).
Figure 4.50
Parameter detail
➢
Sending delay after a bus recovery (seconds)
This parameter lets configure a delay (in seconds) that will be applied after a
bus recovery and, after which, a telegram will be sent.
➢
DPT to be sent
This parameter lets select the DPT type for the value that will be defined in the next
parameter. This value will be sent on a rising edge (contact activated).
Figure 4.51
Parameter detail
➢
Value on rising edge (when contact activated)
This parameter lets define a value for the DTP type configure
d in the “DPT to
be sent” parameter. This value will be sent on a rising edge (contact
activated).