2 / 2
This information is subject to change without prior notice
IntesisBox
is a registered trademark of Intesis Software S.L.U.
email:
web:
phone: +34 938047134
Enclosure
Plastic, type PC (UL 94 V-0)
Net dimensions (d
x
w
x
h): 90x88x56 mm
Recommended space for installation (d
x
w
x
h): 130x100x100mm
Color: Light Grey. RAL 7035
Battery
Size: Coin 20mm x 3.2mm
Capacity: 3V / 225mAh
Type: Manganese Dioxide Lithium
Mounting
Wall.
DIN rail EN60715 TH35.
Console
Port
Mini Type-B USB 2.0 compliant
1500VDC isolation
Terminal Wiring
(for power supply and
low-voltage signals)
Per terminal: solid wires or stranded wires (twisted or with
ferrule)
1 core: 0.5mm
2
… 2.5mm
2
2 cores: 0.5mm
2
… 1.5mm
2
3 cores: not permitted
If cables are more than 3.05 meters long, Class 2 cable is required.
USB port
Type-A USB 2.0 compliant
Only for USB flash storage device
(USB pen drive)
Power consumption limited to 150mA
(HDD connection not allowed)
Power
1 x Plug-in screw terminal block (3 poles)
9 to 36VDC +/-10%, Max.: 140mA.
24VAC +/-10% 50-60Hz, Max.: 127mA
Recommended: 24VDC
Push Button
Button A: Check the user manual
Button B: Check the user manual
Operation
Temperature
0°C to +60°C
Ethernet
1 x Ethernet 10/100 Mbps RJ45
2 x Ethernet LED: port link and activity
Operational
Humidity
5 to 95%, no condensation
Port A
1 x P-Link 1 Plug-in screw terminal block orange (2 poles)
1500VDC isolation from other ports
1 x Plug-in screw terminal block green (2 poles)
Reserved for future use
Protection
IP20 (IEC60529)
LED
Indicators
10 x Onboard LED indicators
2 x Run (Power)/Error
2 x Ethernet Link/Speed
2 x Port A TX/RX
2 x Port B TX/RX
1 x Button A indicator
1 x Button B indicator
Switch A
(SWA)
1 x DIP-Switch for PORTA configuration:
Reserved for future use (leave OFF, default)
PORT B
1 x Serial EIA232 (SUB-D9 male connector)
Reserved for future use
1 x P-link 2 Plug-in screw terminal block (3 poles)
1500VDC isolation from other ports
(except PORT B: EIA232)
Switch B
(SWB)
1 x DIP-Switch for PORTB configuration:
Reserved for future use (leave OFF, default)
CONNECTIONS
ELECTRICAL & MECHANICAL FEATURES
Power Supply
Must use NEC Class 2 or Limited Power Source (LPS) and SELV
rated power supply.
If using DC power supply:
Respect polarity applied of terminals (+) and (-). Be sure the voltage applied is within the range admitted
(check table below). The power supply can be connected to earth but only through the negative terminal,
never through the positive terminal.
If using AC power supply:
Make sure the voltage applied is of the value admitted (24 Vac). Do not connect any of the terminals of the
AC power supply to earth, and make sure the same power supply is not supplying any other device.
Ethernet / BACnet IP (UDP) / Console (UDP & TCP)
Connect the cable coming from the IP network to the connector ETH of the gateway. Use an Ethernet CAT5
cable. If communicating through the LAN of the building, contact the network administrator and make sure traffic
on the port used is allowed through all the LAN path (check the gateway user manual for more information).
With factory settings, after powering up the gateway, DHCP will be enabled for 30 seconds. After that time, if no
IP is provided by a DHCP server, the default IP 192.168.100.246 will be set.
PortA / P-Link 1 Panasonic
Connect the P-Link terminals of Panasonic Outdoor Unit to the connectors A3 and A4
of gateway’s PortA. There
is no polarity to be respected.
PortB / P-Link 2 Panasonic
Connect the P-Link terminals of Panasonic Outdoor Unit to the connectors B1 and B2
of gateway’s PortB. There
is no polarity to be respected.
Console Port
Connect a mini-type B USB cable from your computer to the gateway to allow communication between the
Configuration Software and the gateway. Remember that Ethernet connection is also allowed. Check the user
manual for more information.
USB
Connect a USB storage device (not a HDD) if required. Check the user manual for more information.
Power Supply
Ethernet
BACnet IP
USB
storage
Panasonic
P-Link 2
Console
Port
Panasonic
P-Link 1
100 mm (h)
100 mm (w)
130 mm (d)