background image

  

2 / 2

 

This information is subject to change without prior notice 

IntesisBox

 

is a registered trademark of Intesis Software S.L.U.

 

email

info@intesisbox.com

  

web

www.intesisbox.com 

 

phone: +34 938047134

 

 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 

 

 
 

 

 

 

Enclosure 

Plastic, type PC (UL 94 V-0) 
Net dimensions (d

x

w

x

h): 90x88x56 mm  

Recommended space for installation (d

x

w

x

h): 130x100x100mm 

Color: Light Grey. RAL 7035 

 

Battery 

Size: Coin 20mm x 3.2mm 
Capacity: 3V / 225mAh 
Type: Manganese Dioxide Lithium 

Mounting 

Wall. 
DIN rail EN60715 TH35. 

 

Console 
Port 

Mini Type-B USB 2.0 compliant 
1500VDC isolation 

Terminal Wiring 

(for power supply and 
 low-voltage signals) 

Per terminal: solid wires or stranded wires (twisted or with 
ferrule) 

1 core: 0.5mm

2

… 2.5mm

2

 

2 cores: 0.5mm

2

… 1.5mm

2

 

3 cores: not permitted 

If cables are more than 3.05 meters long, Class 2 cable is required.

 

 

USB port 

Type-A USB 2.0 compliant 
Only for USB flash storage device  

(USB pen drive) 

Power consumption limited to 150mA  

(HDD connection not allowed) 

Power 

1 x Plug-in screw terminal block (3 poles) 

9 to 36VDC +/-10%, Max.: 140mA. 
24VAC +/-10% 50-60Hz, Max.: 127mA 
Recommended: 24VDC 

 

Push Button 

Button A: Check the user manual 
Button B: Check the user manual 

Operation 
Temperature 

0°C to +60°C 

Ethernet 

1 x Ethernet 10/100 Mbps RJ45 
2 x Ethernet LED: port link and activity 

 

Operational 
Humidity 

5 to 95%, no condensation 

Port A 

1 x P-Link 1 Plug-in screw terminal block orange (2 poles) 

1500VDC isolation from other ports 

1 x Plug-in screw terminal block green (2 poles) 

Reserved for future use 

 

Protection  

IP20 (IEC60529) 

LED 
Indicators 

10 x Onboard LED indicators 

2 x Run (Power)/Error 
2 x Ethernet Link/Speed 
2 x Port A TX/RX 

2 x Port B TX/RX 

1 x Button A indicator 
1 x Button B indicator 

Switch A  

(SWA)

 

1 x DIP-Switch for PORTA configuration: 

Reserved for future use (leave OFF, default)

 

 

PORT B 

1 x Serial EIA232 (SUB-D9 male connector) 

Reserved for future use 

1 x P-link 2 Plug-in screw terminal block (3 poles) 

1500VDC isolation from other ports 

           (except PORT B: EIA232)

 

 

 

 

Switch B  

(SWB)

 

 
1 x DIP-Switch for PORTB configuration: 

Reserved for future use (leave OFF, default) 

 

 

 

 

CONNECTIONS 

ELECTRICAL & MECHANICAL FEATURES 

Power Supply 
Must use NEC Class 2 or Limited Power Source (LPS) and SELV

 

rated power supply. 

 

If using DC power supply: 
Respect polarity applied of terminals (+) and (-). Be sure the voltage applied is within the range admitted 
(check table below). The power supply can be connected to earth but only through the negative terminal, 
never through the positive terminal. 

 

If using AC power supply: 
Make sure the voltage applied is of the value admitted (24 Vac). Do not connect any of the terminals of the 
AC power supply to earth, and make sure the same power supply is not supplying any other device. 

 
Ethernet / BACnet IP (UDP) / Console (UDP & TCP) 
Connect  the  cable  coming  from  the  IP  network  to  the  connector  ETH  of  the  gateway.  Use  an  Ethernet  CAT5 
cable. If communicating through the LAN of the building, contact the network administrator and make sure traffic 
on the port used is allowed through all the LAN path (check the gateway user manual for more information).  
With factory settings, after powering up the gateway, DHCP will be enabled for 30 seconds. After that time, if no 
IP is provided by a DHCP server, the default IP 192.168.100.246 will be set. 
 
PortA / P-Link 1 Panasonic 
Connect the P-Link terminals of Panasonic Outdoor Unit to the connectors A3 and A4 

of gateway’s PortA. There 

is no polarity to be respected. 
 
PortB / P-Link 2 Panasonic 
Connect the P-Link terminals of Panasonic Outdoor Unit to the connectors B1 and B2 

of gateway’s PortB. There 

is no polarity to be respected. 
 
Console Port
 
Connect  a  mini-type  B  USB  cable  from  your  computer  to  the  gateway  to  allow  communication  between  the 
Configuration Software and the gateway. Remember that Ethernet connection is also allowed. Check the user 
manual for more information. 
 
USB 
Connect a USB storage device (not a HDD) if required. Check the user manual for more information. 

Power Supply 

Ethernet 
BACnet IP 

USB  
storage 

Panasonic      
P-Link 2  

 

Console 
Port 

Panasonic      
P-Link 1  

 

100 mm (h) 

100 mm (w) 

130 mm (d) 

Reviews: