6.1.2. Multiple Membrane Station Controller with Remote Monitoring and Control
The multi-station controller is for commercial scale applications where multiple AQUALOOP stations are
required. The base unit accommodates up the three AQUALOOP stations and controls all system functions
and monitoring. Expansion units each add control up to three additions stations. The local interface is touch
screen. The panel connects with building management systems via MODBUS or BacNet connectivity.
Through the
link, full remote programming, control, monitoring and history is
possible, depending on level of access.
AL-CUNIT-M-230/480V
AL-CUNIT-M2 208/480V
Dimensions (H x W x D):
600 x 600 x 210 mm
23.6 x 23.6 x 8.5 “
Mains supply central controller:
230 / 400 V AC / 50 Hz
208 / 480 V AC / 60 Hz
Power outputs:
-
Blowers:
230 V AC / 50 Hz
208/ 480 V AC / 60 Hz
-
Sludge pumps:
-
Ball valves (3 ways):
-
Solenoid valves (2 ways):
230 V AC / 50 Hz
230 V AC / 50 Hz
230 V AC / 50 Hz
208/ 480 V AC / 60 Hz
208/ 480 V AC / 60 Hz
208/ 480 V AC / 60 Hz
Low voltage outputs (24V DC):
-
Filtration pumps:
-
Backwash pumps:
-
Warning light (red)
-
Alarm beeper
24 V DC
24 V DC
24 V DC
24 V DC
24 V DC
24 V DC
24 V DC
24 V DC
Low voltage outputs (12V DC):
-
Controller/ Display
12 V DC
12 V DC
Signal inputs:
-
Level pressure sensor, bioreactor:
4 … 20 mA
4 … 20 mA
-
Level pressure sensor, clear water
tank:
-
Water meter
4 … 20 mA
1 L/ Imp or 4 … 20 mA
4 … 20 mA
1 L/ Imp or 4 … 20 mA
Bus connection (to Exp. controller):
OUT
OUT
Interface:
RJ45
RJ45
Display size:
10”, resistive
10”, resistive
Protection type:
IP 41
IP 41
Material unit case:
Sheet steel
Sheet steel
Remote control interface:
RJ45
RJ45
Interface Protocol:
Bacnet, Modbus, Encrypted
HTTPS
Bacnet, Modbus, Encrypted
HTTPS
Remote Monitoring and Control
Protocol:
Encrypted HTTPS connection /
VPN
Encrypted HTTPS connection
/ VPN
Certification:
CE
UL 508A (UL Panel Label)
Note: Detailed electrical connections, programming, and set up are described in sections 7.1.2 through 7.2.2.5.
Summary of Contents for AQUALOOP GW 10800
Page 12: ...11 Fig AQUALOOP System 1200 L day 317 GPD Fig AQUALOOP System 1800 L day 476 GPD...
Page 13: ...12 Fig AQUALOOP System 3600 L day 952GPD Fig AQUALOOP System 5400 L day 1428 GPD...
Page 37: ...36 Fig Electrical connection plan upper pump lower pump...
Page 39: ...38 Fig Control cabinet of multiple membrane station controller...
Page 42: ...41 7 1 3 Expansion membrane station controller Fig Control cabinet of expansion controller...
Page 89: ...88 Designed and provided by INTEWA GmbH or to be separately approved alternative...
Page 90: ...89 INTEWA GmbH Version 1 1 a Subject to technical changes...