47
SPECIFICATIONS
aV100 extract air system – Avio N 100
•
Installation and operating instructions
Hygrostat (optional)
Feature
Value
Type of protection
IP 30D
Measuring range/adjustment range
35 % – 95 % RH / 30% – 100 % RH
Compensation time
20 minutes – 40 minutes
(depending on airflow)
Switching differential
Approx. 4% RF at 50% RF
Switching capacity
AC 250 V, 0.1 A – 5 A (with resistive load)
Contact
Changer, 1 pole (NO or NC)
Ambient temperature
-40°C – 60°C
Working temperature
0°C – 60°C
Width x Height x Depth
81 mm x 81 mm x 28 mm
Weight
Approx. 60 g
Wall sleeve
Components
Length/
depth (mm)
Dimensions
(mm)
Weight (g)
Sleeve of wall sleeve
300
Ø 107
270
with pre-installed non-return valve
Tube of wall sleeve
280
Ø 103
180
Wall sleeve extension
Identical to the wall sleeve,
without non-return valve and fixing elements
Flat duct
Designation
Length/
depth (mm)
dimensions
(W x H in
mm)
Weight (g)
Flat duct 60x204x500 (D100) Corner
500
204 x 60
668
Flat duct 60x204x1000 (D100) Corner
1000
204 x 60
1296