Then mount the wall sleeve in the wall opening. The installation of the wall sleeve is not included
in this document. It can be found in the installation instructions for your specific ventilation device.
The wall opening for the Connect inner cover is also the wall opening in which the ventilation
device is installed. The Connect inner cover replaces the inner cover of the respective ventilation
device. The exact installation position can be found in the ventilation concept. Consult your plan-
ner before installation if you are at all uncertain. The installation of the other components of the
ventilation device is not part of this documentation. This can be found in the separate installation
instructions for the respective ventilation device.
25
inVENTer Connect controller platform | Installation instructions
PREPARING FOR INSTALLATION
Requirements:
• The masonry must be dry and in a load-bearing
condition.
• No load-bearing elements in the position of the drill
hole.
NOTE:
Accumulation of condensate in the wall
sleeve
leads to damage to the brickwork and
exterior wall!
• Create the wall opening with a slope of
1° to 2° to the exterior wall.
►
Make the wall opening (core hole) for the ventilation
device for mounting the Connect inner cover
(for position, see separate installation instructions
for the respective ventilation device and concept).
►
Drill a wall opening
• Ø 225 mm for wall sleeve R-D200
• Ø 180 mm for wall sleeve R-D160
with a slope of 1° to 2° to the exterior wall.
The wall opening for the ventilation device has been
created.
Creating a wall opening for the Connect inner cover
Additionally for installation of the ventilation device with flush-mounted Connect UP inner cover:
►
Create an opening for the flush-mounted housing
on the inside wall, centred on the core drill hole,for
installing the inner cover.
Dimensions: 245 x 245 x 40 (W x H x D, mm)
245
40
Ø
225
ø 180
→ R-D160
ø 225
→ R-D200
1 – 2°
!