38
39
SPECIFICATIONS
SPECIFICATIONS
iV-Compact ventilation system
•
Installation and operating instructions
iV-Compact ventilation system
•
Installation and operating instructions
Specifications according to EC Directive for energy related products,
regulation 1254/2014 [Germany]
iV-Compact, local demand control:
Product fiche iV-Compact according to VO 1254/2014 EU, dated 2014-07-11
Pt.
Description
Data
a
Supplier's name
inVENTer GmbH
b
Supplier's model identifier
iV-Compact
c
SEC class / Specific energy con
-
sumption [kWh/(m²a)]
cold
-81.498
average
A
-40.735
warm
-17.383
d
Typology
BVU
e
Type of drive installed
2
f
Type of heat recovery system
regenerative
g
Thermal efficiency of heat recovery ƞ
t
[%]
72
h
Maximum flow rate (supply air) [m³/h]
58
i
Electric power input [W]
6
j
Sound power level L
wa
[dB (A)]
53
k
Reference flow rate [m³/h]
40.6
l
Reference pressure difference [Pa]
0
m
Specific power input (SPI) [W/m³/h]
0.13
n
Control factor
0.65
o
Internal/external leakage rate [%]
n. a.
p
Mixing rate [%]
n. a.
q
Position of visual filter warning
Controller
r
Regulated supply and exhaust grilles in the facade
(one-direction devices only)
no
s
Internet
t
Airflow sensitivity [%]
29.3
u
Indoor and outdoor air tightness [m³/h]
n. a.
v
Annual electricity consumption [kWh/(m²a)]
0.76
w
Annual heating saved [kWh/(m²a)]
cold
83.39
average
42.63
warm
19.28
iV-Compact, manual control:
Product fiche iV-Compact according to VO 1254/2014 EU, dated 2014-07-11
Pt.
Description
Data
a
Supplier's name
inVENTer GmbH
b
Supplier's model identifier
iV-Compact
c
SEC class / Specific energy con
-
sumption [kWh/(m²a)]
cold
-72.195
average
A
-34.715
warm
-13.245
d
Typology
BVU
e
Type of drive installed
2
f
Type of heat recovery system
regenerative
g
Thermal efficiency of heat recovery ƞ
t
[%]
72
h
Maximum flow rate (supply air) [m³/h]
58
i
Electric power input [W]
6
j
Sound power level L
wa
[dB (A)]
53
k
Reference flow rate [m³/h]
40.6
l
Reference pressure difference [Pa]
0
m
Specific power input (SPI) [W/m³/h]
0.13
n
Control factor
1
o
Internal/external leakage rate [%]
n. a.
p
Mixing rate [%]
n. a.
q
Position of visual filter warning
Controller
r
Regulated supply and exhaust grilles in the facade
(one-direction devices only)
no
s
Internet
t
Airflow sensitivity [%]
29.3
u
Indoor and outdoor air tightness [m³/h]
n. a.
v
Annual electricity consumption [kWh/(m²a)]
1.79
w
Annual heating saved [kWh/(m²a)]
cold
76.67
average
39.19
warm
17.72