INSTALLATION AND ASSEMBLY

INSTALLATION AND ASSEMBLY

Ventilation System iV-Twin+ 

 Installation and Operating Instructions

Ventilation System iV-Twin+

 

 Installation and Operating Instructions

4.2 

Create wall opening

CAUTION

Falling masonry when creating the wall opening

leads to injury to body parts and/or damage to objects!

•  Install protection against falling masonry on the outside of the building.

•  Remove objects from the immediate vicinity of the outside of the building.

Drilling machine with attachment core drill or milling drill Ø 225 mm, 

Option Simplex additionally cut-off grinder and spirit level

Positioning of the wall sleeve 

(

 3.1 – mounting position): 

Minimum distance to adjacent components on the outer wall (observe insulation thickness / 

roller shutters): 

upwards: 450 mm from bore centre / centre axis. 

  

 

downwards/laterally: 250 mm from bore centre/ centre axis. 

Minimum distance to components on the inner wall 250 mm from bore centre

Minimum distance in front: 300 mm for cleaning and maintenance work 

Do not place the wall opening near radiators.

In new buildings and for timber-frame construction, we recommend the use of the optional D200 

wall mounting block or the Simplex wall mounting system.

Create wall opening through core drilling

Prerequisite: 

The masonry is dry and stable. 

No load-bearing elements in the position of the 

borehole.

 

Drill a wall opening, Ø 225 mm with a gradient of 

1 – 2° to the outer wall.

Ø

 225 

NOTE

Condensate accumulating in the 

wall sleeve 

will damage the masonry and 

outer wall!

•  Create a wall opening with a slope of 1 – 2° 

to the outer wall.

1 – 2°

 

The wall opening for the ventilation unit has been 

created.

Use the Simplex wall installation system.

Prerequisite: 

The construction project is in the shell construction 

phase.

Y

 

Insert the Simplex wall installation system into the 

masonry at the appropriate point.

Observe 

the installation markings on/in the wall 

installation sleeve (red arrow): The integrated 

slope is directed towards the outer wall to ensure 

that any condensate that may form can drain off.

 

Wall-in the mounting block into the masonry.

 

Apply insulation, interior and exterior plaster.

4.3 

Installing the fan BUS

Schematic sketches for the wiring of the ventilation units:

In a row:

Y

 

Make sure that the outer wall has a protrusion Y 

of 10 mm.

 

Install the fan BUS (

 4.3).

 

Continue with the installation of the weather 

protection hood (

 4.5). 

Star-shaped:

Power supply

Power supply

Control unit

Control unit

Connection 

clamps

Ventilation units

Ventilation 

units

 

The Simplex wall mounting system is installed.

 

Align the fastening elements.

Cable type LiYY, 3-wire, length see 

 controller

Cable type LiYY, 3-wire, max 33 m

Summary of Contents for iV-Twin+

Page 1: ...iV Twin Installation and Operating Instructions ...

Page 2: ...al 42 11 Warranty and manufacuter s warranty 44 12 Service 44 13 Attachment 1 Cleaning protocol 45 TABLE OF CONTENTS Trademarks copyrights and industrial property rights inVENTer Xenion and Clust Air are protected trademarks of inVENTer GmbH The copyright of this document remains with the manufacturer Rights to all content and images inVENTer GmbH 2014 19 All trademarks used in this documentation ...

Page 3: ... to comply with safety regulations can lead to personal injury and or damage to property Intended use The ventilation unit is used for the ventilation of living spaces and similar residential spaces They are controlled by a controller of the inVENTer system General information When installing the device system observe the applicable standards regulations and directives In particular the applicable...

Page 4: ...ve the cable sheath completely from the fan BUS to avoid cable breakage when inserting the inner cover otherwise the inner cover cannot be inserted When using several ventilation units controlled by several controllers you must ensure that the ventilation units are synchronized with each other see Installation and Operating instructions for Controllers You should connect all controllers via a main...

Page 5: ...ptically discreet to the interior Outside the components of the ventilation unit are concealed by a rain proof cover The air volume flow separators integrated in the inner cover and outer panel ensure that no mixing of different air volume flows takes place outside the wall sleeve The standard length of the wall sleeve is 495 mm For larger wall thicknesses a wall sleeve with a length of 745 mm can...

Page 6: ...e controller then switches the ventilation unit back to the originally set operating mode Function of the iV Twin in reversing mode In standard operation the ventilation system works according to the principle of regenerative heat recovery The integrated heat accumulator is charged with the thermal energy of the room air when it flows to the outside exhaust air After 70 seconds the reversing fan c...

Page 7: ... 11 Off Pause function The sMove and MZ Home controller can be extended with additional sensors An external interface enables the connection of a potential free switching contact or integration into an existing house control system via an analogue input Detailed information can be found in the installation and operating instructions for the controller 3 Installation preparation 3 1 Installation lo...

Page 8: ...lintel4 250 250 1 260 249 Ø225 148 165 148 165 250 3 4 5 6 250 1 279 5 6 2 1 279 450 2 450 2 4 4 4 3 1 Position wall opening Position wall installation system Simplex 3 3 Dimensions Description Depth Length mm Width mm Height mm Wall thickness1 270 Wall opening for wall sleeve Wall thickness1 Ø225 Wall sleeve R D200x495 745 495 745 Ø200 Weather protection hood Flex Twin 23 88 279 313 Inner cover F...

Page 9: ...ather protection hood 2 Separating element Flex Twin pre assembled 3 Mounting hole outer wall Ø 8 mm min 50 mm deep 4 x 4 Mounting hole Simplex 4 x 5 Guide for sealing strip 6 Weather protection hood cover 7 Protective grilles 8 Drip edge Inner cover Flair Twin Figure 6 Dimensioned drawing inside panel Flair Twin V 233x233 1 Cover inner panel 2 Separating element inside panel pre assembled 3 Space...

Page 10: ... through core drilling Prerequisite The masonry is dry and stable No load bearing elements in the position of the borehole Drill a wall opening Ø 225 mm with a gradient of 1 2 to the outer wall Ø 225 NOTE Condensate accumulating in the wall sleeve will damage the masonry and outer wall Create a wall opening with a slope of 1 2 to the outer wall 1 2 Ö The wall opening for the ventilation unit has b...

Page 11: ...unit and wall opening Make sure to approach the plaster wall slot for the cable to the control unit at an angle of 45 to the bottom left of the wall opening Seal the wall opening from the inside and outside until the wall installation sleeve is inserted Ö The plaster wall slot for the cable fan BUS has been created NOTE The use of a wire cross section that is too small leads to an excessively high...

Page 12: ... wall installation sleeve Observe the necessary sealing levels Cut off the 2 component mounting foam and protruding mounting wedges flush with the outer and inner walls Make sure that you do not damage the fan BUS 4 5 Mount the external closure NOTE Mounting on unfinished outer wall leads to damage of the outer wall Do not install the external closure until the external wall has been completed and...

Page 13: ...ed After placing the cover seal the joints between the cover and the façade with permanently elastic external sealing compound on both sides and at the top Ö The Flex Twin weather protection hood is installed Push the air volume flow separation vertically into the wall sleeve Make sure that the air volume flow separation is pushed into the holder of the weather protection hood The separating eleme...

Page 14: ...ood Make sure that the handle points in the direction of the interior Make sure that the fan BUS protrudes into the interior Pass one of the fan cables under the sealing lip in such a way that all lines are in the chamber with the fan BUS Shorten the fan BUS 3 wire to your determined wall thickness minus 260 mm Remove the complete cable sheath from the fan BUS Insulate the lines on the fan BUS by ...

Page 15: ...n Installation and Operating Instructions Ventilation System iV Twin Installation and Operating Instructions 4x CLICK Remove the thread locking devices from the fastening elements of the wall sleeve Place the baseplate inner cover centrically to the wall sleeve on the inner wall Make sure that the marking arrow on the base plate points upwards Screw the baseplate inner cover together with 4 screws...

Page 16: ...nality and performance of the iV Twin ventilation system Depending on requirements and or air quality your individual cleaning schedule may differ from these recommendations Interval Component Cleaning action Cleaning from inside Monthly Pollen filter Replace the used filters Inner cover Clean the surface of the cover with a damp cloth Quarterly Dust filter Wash the dust filters in warm water Or R...

Page 17: ...nstallation and Operating Instructions Disconnect the two plugs of the fan connectors The three connection terminals cable to the controller are not detached Ö You have cleaned exchanged the dust filter Pull the two fan units by the knob out of the wall sleeve Make sure to carefully remove the plug connection under the separating plate without loosening the BUS plug connection Turn the fan units s...

Page 18: ...he heat accumulator 6 3 Cleaning the heat accumulator Prerequisite The ventilation unit is disconnected from the power supply The fan unit is removed 6 2 Push the heat storage tank half cylinders to the right and left of the separating element from the interior up to the stop in the direction of the weather protection hood Make sure that the handle points in the direction of the interior Make sure...

Page 19: ...6 Power consumption W 0 5 3 Volume flow related electrical fan power W m h 0 18 Safety class DIN EN 61140 III Protection class DIN EN 60529 IPX4 Filter class Standard filter DIN EN 779 2012 G3 Antifreeze Automatic by reversing operation down to 20 C Weight g 7500 Conformity Energy efficiency class A A 7 2 Energy label iV Twin according to ErP directive regulation 1254 2014 You will find the follow...

Page 20: ...address www inventer de t Pressure fluctuation sensitivity 44 5 u Air tightness between inside and outside m h 3 2 v Annual power consumption kWh m a 1 05 w Annual savings Heating energy kWh m a cold 93 06 average 47 57 hot 21 51 Ventilation unit iV Twin manually controlled Product data sheet iV Twin according to VO 1254 2014 EU of July 11 2014 No Description Parameters a Vendor inVENTer GmbH b Mo...

Page 21: ...t Number Dust filter iV Twin 1 Set 1004 0192 Pollen filter iV Twin 1 Set 1004 0193 Activated carbon filter iV Twin 1 Set 1004 0194 Sound protector SPR iV Twin 2 x 1004 0189 Sound protection insert iV Twin 2 x 1004 0190 Component Product Number Round cable LiYY O 3x0 75 33m 1004 0020 Mounting wedge set block with 16 wedges 3009 0012 Styrofoam disk R D196x30 for wall sleeve 3007 0088 Simplex 365 inc...

Page 22: ...wer power level on the controller Fault Possible cause Correction Supply air cold Installation error Check the position of the plug on the controller The plug must be firmly fixed in the connector housing Disassembly Disassemble the ventilation unit in reverse order You can then dispose of your old unit Observe the instructions below Disposal recommendations Disposal The products described in thes...

Page 23: ...esentative Warranty and guarantee claims In the event of a warranty or guarantee claim contact the dealer or factory representative responsible for you Always return the complete device to the manufacturer The warranty claim is an additional offer of the manufacturer and does not affect any applicable law Accessories and spare parts To order components for your ventilation unit please contact your...

Page 24: ...A HRB 510380 RIGHTS TO ALL CONTENT PICTURE CREDITS INVENTER GMBH 2014 19 SUBJECT TO TECHNICAL CHANGES WITHOUT NOTICE ALL INFORMATION WITHOUT GUARANTEE NO LIABILITY IS ASSUMED FOR ANY MISPRINTS IMPRESSUM Date Number of inspected devices Cleaning inspection activity1 Comment Name Signature Component A B C 1 Cleaning Inspection Activity Inspection I Cleaning C Replacement R Component Name Scope Activ...

Page 25: ...r de Version 07 2019 Subject to technical changes without notice Product Number 5004 0004 inVENTer GmbH 2014 19 inVENTer GmbH Ortsstraße 4a D 07751 Löberschütz 49 0 36427 211 0 49 0 36427 211 113 info inventer de ...

Reviews: