38
inVENTer
®
iV12-Smart
®
/iV12-Smart
®
Corner ventilation system
•
Installation and operating instructions
installing an embrasure lattice
noTe
Installation on an uninished external wall.
Damage to the external wall!
► Only install embrasure lattice once external wall is inished and is properly hardened.
Requirements
External wall inished and level.
Flat tube is installed.
Adhesive tape removed from lat tube opening.
►
Afix sealing tape 9 mm (1) on external wall side
to sides and around outer edge of embrasure
lattice (2).
►
Ensure that the sealing tape (1) is affixed at
the top and bottom between the
through hole (3) and the condensate drain
(4).
1
2
3
4
►
Secure embrasure lattice (7) using screws (8) to
ixings (6) on sliding sleeve (5).
►
Ensure that louvres (9) of embrasure lattice
deflect air flow away from window area.
7
5
8
6
9
►
Bend top drip rail (10) down.
0
1
Ö
Ö
Embrasure lattice is installed.
assembly anD insTallaTion