19
ASSEMBLY AND INSTALLATION
inVENTer PAX standard set
•
Installation and operating instructions
4.3
Install the mounting plate
CAUTION
Falling main module.
Injury to persons and/or damage to property!
►
Verify the load-bearing capacity of the ceiling/interior wall.
Rawl plugs, screws, screw driver
Requirements:
Boreholes are drilled.
Ceiling/interior wall must be dry and in a load-bearing condition.
Ö
The mounting plate is installed.
4.4
Insert the wall ducts
NOTICE
Accumulation of condensate in the wall duct and interruption of the thermal insulation
composite system.
Damage to exterior wall/masonry and the building structure.
►
Attach the wall ducts with a slope of 1 – 2° to the exterior wall.
►
Replace the wall construction as far as the wall ducts.
►
Observe the necessary barrier levels.
►
Screw the mounting plate to the interior wall
with 6 screws.
Makes sure that
the designations EA (extract
air) and OA (outdoor air) are readable and
located in direction of the wall openings.
►
Insert the rawl plugs into the boreholes on the
ceiling.