16
Pulsar extractor fan
•
Installation and operating instructions
5
Installation
5.1 Creating the wall opening and installing the wall sleeve
DANGER
Ingress of water into the Pulsar extractor fan.
Electric shock and overheating due to short circuit (230V, 50Hz)!
►
Create wall opening for Pulsar extractor fan outside protection area 0.
CAUTION
Falling masonry when creating the wall opening.
Injury to persons and/or damage to property!
►
Use adequate protection against falling masonry. Remove objects from the immediate vicinity.
Milling drill with ø 115 mm, wall sleeve (e.g. from aV100 wall installation set)
Requirements:
The masonry must be dry and in a load-bearing condition.
There must be no load-bearing elements at the location of the planned borehole/plaster or wall slot.
NOTICE
Accumulation of condensate in the wall sleeve.
Damage to the exterior wall and masonry!
►
Create the wall opening with a slope of 1 – 2° to the exterior wall.
►
Drill a wall opening, Ø 115 mm, with a slope of 1 – 2° to
the exterior wall.
►
Create the plaster/masonry slot between the power source/
switch and the wall opening.
For positioning options,
refer to
5, page 22.
Ø
115
INSTALLATION