40
| Optidrive Eco User Guide |
Version 3.06
www.invertekdrives.com
9. Extended Parameters
9.1. Parameter Group 2 – Extended parameters
Par.
Parameter Name
Minimum
Maximum
Default
Units
P2-01
Preset Frequency / Speed 1
-P1-01
P1-01
50.0 (60.0)
Hz / Rpm
P2-02
Preset Frequency / Speed 2
-P1-01
P1-01
40.0
Hz / Rpm
P2-03
Preset Frequency / Speed 3
-P1-01
P1-01
25.0
Hz / Rpm
P2-04
Preset Frequency / Speed 4
-P1-01
P1-01
P1-01
Hz / Rpm
Preset speeds can be selected by:
Configuring P1-13 to an option that permits logic selection via the digital inputs (see section
8.1. Digital Input Configuration
Parameter P1-13
).
Using the user defined logic configuration parameters in Parameter Group 9.
Configured through the drive PLC function using the OptiTools Studio Suite PC software.
P2-05
Preset Speed 5 / Clean 1
-P1-01
P1-01
0.0
Hz /Rpm
Preset speed 5 is automatically reference by the Pump Clean function when this is enabled. When the Pump Clean function is disabled,
Preset speed 5 can be selected as per preset speeds 1 – 4.
P2-06
Preset Speed 6 / Clean 2
-P1-01
P1-01
0.0
Hz / Rpm
Preset speed 6 is automatically reference by the Pump Clean function when this is enabled. When the Pump Clean function is disabled
Preset speed 6 can be selected as per as per preset speeds 1 – 4.
P2-07
Preset Speed 7 / Boost 1 / Pump Stir Speed
-P1-01
P1-01
0.0
Hz / Rpm
Preset speed 7 is automatically referenced by the Start / Stop Boost function, or the Pump Stir Function, when these functions are
enabled. When they are disabled, Preset speed 7 can be selected as per preset speeds 1 – 4.
P2-08
Preset Speed 8 / Boost 2
-P1-01
P1-01
0.0
Hz / Rpm
Preset speed 8 is automatically reference by the Start / Stop Boost function when this function is enabled. When disabled, Preset
speed 8 can be selected as per preset speeds 1 – 4.
P2-09
Skip Frequency Centre Point
P1-02
P1-01
0.0
Hz / Rpm
Defines the centre point of the skip frequency band. The width of the skip frequency band is defined by:
Lower limit = P2-09 - P2-10/2
Upper limit = P2-09 + P2-10/2
All skip frequency bands defined for forward speeds are mirrored for negative speeds.
P2-10
Skip Frequency Band Width
0.0
P1-01
0.0
Hz / Rpm
Defines the width of the skip frequency band. The width of the skip frequency band is defined by:
Lower limit = P2-09 - P2-10/2
Upper limit = P2-09 + P2-10/2
All skip frequency bands defined for forward speeds are mirrored for negative speeds.
P2-11
Analog Output 1 Function
0
12
8
-
Digital Output Mode. Logic 1 = +24V DC
0
Drive running
Logic 1 when the Optidrive is enabled (Running).
1
Drive healthy
Logic 1 When no Fault condition exists on the drive.
2
At speed
Logic 1 when the output frequency matches the setpoint frequency.
3
Motor speed > 0
Logic 1 when the motor runs above zero speed.
4
Motor speed >= limit
Logic 1 when the motor speed exceeds the adjustable limit.
5
Motor current >=limit
Logic 1 when the motor current exceeds the adjustable limit.
6
Motor torque >= Limit
Logic when the motor torque exceeds the adjustable limit.
7
Analog input 2 >=limit
Logic when the signal applied to the Analog Input 2 exceeds the adjustable limit.
NOTE
When using settings 4 – 7, parameters P2-16 and P2-17 must be used together to control the behaviour. The output will switch
to Logic 1 when the selected signal exceeds the value programmed in P2-16, and return to Logic 0 when the signal falls below the
value programmed in P2-17.
Analog Output Mode
8
Motor speed
0 to P1-01.
9
Motor current
0 to 200% of P1-08.
10
Motor torque
0 to 200% of motor rated torque.
11
Motor power
0 to 150% of drive rated power.
12
PID Output
Output from the internal PID Controller, 0 – 100%.
9
Extended P
arameters