Goodrive18 series two-in-one VFD Function parameters and function terminal reuse
-38-
Function
code
Name
Description
Default
value
Modify
stop
frequency reaches the starting frequency
determined by P01.09.
Wait time before DC braking: The VFD blocks
the output before starting DC braking. After this
wait time, the DC braking will be started so as to
prevent over-current fault caused by DC braking
at high speed.
DC braking current at stop: The value of P01.11
is the percentage of rated current of VFD. The
bigger the DC braking current is, the greater the
braking torque is.
DC braking time at stop: It indicates the retention
time of DC braking. If the time is 0, the DC
braking is invalid, and the VFD will coast to stop.
P01.04
ACC
P1314
.
P0123
.
Constant
speed
In running
DEC
P0110
.
P1315
.
P01.12
P01.09
t
Setting range of
: 0.00Hz
(Max.
output frequency)
Setting range of
: 0.00
–50.00s
Setting range of
: 0.0
–100.0% (rated
current peak of the VFD)
Setting range of
: 0.00
–50.00s
P01.10
Wait time before
DC braking
0.00s
○
P01.11
DC braking
current at stop
0.0%
○
P01.12
DC braking time
at stop
0.00s
○
P01.13
FWD/REV
running
deadzone time
This function code indicates the transition time
specified in
during FWD/REV rotation
switching.
Output frequency
FWD
REV
T
Starting
frequency
Shift after the
zero frequency
Shift after the
starting frequency
Deadzone
time
Setting range: 0.0
–3600.0s
0.0s
○