Goodrive18 series two-in-one VFD Function parameters and function terminal reuse
-40-
Function
code
Name
Description
Default
value
Modify
started automatically after the initialization.
Note:
Exercise caution before using this
function. Otherwise, serious result may follow.
P01.19
Action
performed when
the running
frequency is
lower than the
lower frequency
limit (valid when
the lower
frequency limit
is greater than
0)
This function code determines the running state
of the VFD when the set frequency is lower than
the lower-limit one.
0: Run at the lower-limit frequency
1: Stop
2: Sleep
The VFD will coast to stop when the set
frequency is lower than the lower-limit one. If the
set frequency exceeds the lower limit one again
and it lasts for the time set by
, the VFD
resumes the running state automatically.
0
◎
P01.20
Delay for
recovery from
hibernation
This function code determines the sleep delay
time. When the running frequency of the VFD is
lower than the lower limit one, the VFD becomes
standby.
When the set frequency exceeds the lower limit
one again and it lasts for the time set by
the VFD will run automatically.
Setting frequency
running
sleep
t1
t2
running
t
t1
<
t3, so the VFD does not work
t1+t2=t3, so the VFD works
T3=P01.20
t3
Setting range: 0.0
–3600.0s (valid when
=2)
0.0s
○
P01.21
Restart after
power outage
This function code indicates whether the VFD
automatically runs after re-power on.
0: Disable
1: Enable. If the restart condition is met, the VFD
will run automatically after waiting the time
defined by
0
○
P01.22
Wait time for
restart after
This function code indicates the wait time before
the automatic running of the VFD that is
1.0s
○