Goodrive18 series two-in-one VFD Function parameters and function terminal reuse
-51-
Function
code
Name
Description
Default
value
Modify
P04.09
V/F slip
compensation
gain
This function code is used to compensate the
motor rotation speed change caused by load
change during SVPWM control to improve the
rigidity of the motor. The rated slip frequency of
the motor needs to be calculated.
△
f=f
b
-n*p/60
Of which, f
b
is the rated frequency of the motor,
its function code is
. n is the rated rotating
speed of the motor and its function code is
. p is the pole pair of the motor. 100.0%
corresponds to the rated slip frequency
△
f.
Setting range: 0.0
–200.0%
100.0%
○
P04.10
Low frequency
vibration control
factor
In the SVPWM control mode, current fluctuation
may occur to the motor on some frequency,
especially the motor with big power. The motor
cannot run stably or overcurrent may occur.
These phenomena can be canceled by adjusting
the parameters.
Setting range of
: 0
–100
Setting range of
: 0.00Hz
(Max.
output frequency)
10
○
P04.11
High frequency
vibration control
factor
10
○
P04.12
Vibration control
threshold
30.00 Hz
○
P04.26
Energy-saving
operation
selection
0: No operation
1: Automatic energy-saving operation
The motor on the light load conditions,
automatically adjusts the output voltage to save
energy.
0
◎
P04.27
Channel of
setting voltage
This function code is used to select the output
voltage setting channel at V/F curve separation.
0: Keypad. The output voltage is determined by
1: Reserved
2: AI2
3: AI3
4: Reserved
5: Multi-step speed
6: PID
7: MODBUS communication
0
○
Summary of Contents for GD18-004-4-2