Goodrive18 series two-in-one VFD Function parameters and function terminal reuse
-54-
Function
code
Name
Description
Default
value
Modify
29: Torque control prohibition
30: ACC/DEC prohibition
31: Counter trigger
32: Reserved
33: Cancel the frequency change setting
temporarily
34: DC brake
35: Reserved
36: Shift the command to the keypad
37: Shift the command to the terminals
38: Shift the command to the communication
39: Pre-magnetized command
40: Clear the power consumption
41: Keep the power consumption
42: Emergency stop
43
–60: Reserved
61: PID pole switching
62
–63: Reserved
When terminals use the ACC/DEC time selection
function, it is required to select four groups of
ACC/DEC time via state combination of these
two terminals.
Tml1
Tml2
ACC/DEC
Function code
OFF
OFF
ACC/DEC time1
ON
OFF
ACC/DEC time2
OFF
O N
ACC/DEC time3
ON
ON
ACC/DEC time4
P05.10
Polarity
selection of the
input terminals
This function code is used to set the polarity of
the input terminals.
When the bit is 0, the input terminal is anode.
When the bit is 1, the input terminal is cathode.
BIT8
BIT7
BIT6
BIT5
BIT4
S8
S7
S6
S5
BIT3
BIT2
BIT1
BIT0
S4
S3
S2
S1
Setting range: 0x000
–0x1FF
0x000
○
P05.11 Switch filter time This function code is used to set the filter time of 0.010s
○