Goodrive18 series two-in-one VFD Function parameters and function terminal reuse
-57-
Function
code
Name
Description
Default
value
Modify
generated by FWD or REV, and they control the
running direction. During running, the terminal
Sin should be closed, and terminal FWD or REV
generates a rising edge signal to control the
running and direction of VFD; the VFD should be
stopped by disconnecting terminal Sin.
FWD
REV
COM
SB1
SB3
SB2
Sin
Sln
FWD
REV
Running
direction
ON
OFF→ON
ON
Forward
OFF
Forward
ON
ON
OFF→ON
Reverse
OFF
Reverse
ON→OFF
/
/
Decelerate
to stop
/
/
Sln: 3-wire control, FWD: Forward running, REV:
Reverse running
Note:
In the 2-wire running mode, when the
FWD/REV
terminal is valid, but the VFD stops
because of the stopping command from another
source, even when the control terminal
FWD/REV
keeps valid, the VFD does not run
after the stopping command is terminated. Only
when
FWD/REV
is re-triggered, the VFD can
start again, for example, the PLC single-cycle
stop, fixed-length stop and terminal-controlled
valid
STOP/RST
P05.14
S1 terminal
switching on
delay time
The function codes define the corresponding
delay time of electrical level change when the
programmable terminals are switched on to
0.000s
○