Goodrive18 series two-in-one VFD Function parameters and function terminal reuse
-91-
Function
code
Name
Description
Default
value
Modify
9: No check (N, 7, 2) for ASCII
10: Even check (E, 7, 2) for ASCII
11: Odd check (O, 7, 2) for ASCII
12: No check (N, 8, 1) for ASCII
13: Even check (E, 8, 1) for ASCII
14: Odd check (O, 8, 1) for ASCII
15: No check (N, 8, 2) for ASCII
16: Even check (E, 8, 2) for ASCII
17: Odd check (O, 8, 2) for ASCII
P14.03
Communication
response delay
0
–200ms
This function code indicates the time interval
between when the VFD receives data and when
the VFD sends a response to the upper monitor.
If the delay is shorter than the system processing
time, the delay is the system processing time. If
the delay is longer than the system processing
time, even though the data has been processed,
the VFD does not send a response to the upper
monitor until the delay is reached.
5
○
P14.04
Communication
timeout time
0.0 (invalid), 0.1
–60.0s
When this function code is set to 0.0, the
communication timeout time parameter is invalid.
When this function code is set to a non-zero
value, if the time interval between two
communications exceeds the communication
timeout ime, the fault "RS485 communication
fault" (CE) is reported.
In common cases, it is set to 0.0. In systems
which have continuous communication, you can
monitor the communication condition by setting
this function code.
0.0s
○
P14.05
Transmission
fault processing
0: Alarm and stop freely
1: Not alarm and continue to run
2: Not alarm and stop according to the stop
means (only under communication control)
3: Not alarm and stop according to the stop
means (under all control modes)
0
○