Goodrive18 series two-in-one VFD Function parameters and function terminal reuse
-30-
Function
code
Name
Description
Default
value
Modify
Carry out command control by using RUN or
STOP/RST on the keypad. When the
multifunction key QUICK/JOG is set to
FWD/REVC shifting function (
=3), the
key can be used to change the running direction.
You can press
RUN
and
STOP/RST
simultaneously in running state to make the VFD
coast to stop.
1: Terminal (LOCAL/REMOT blinking)
Carry out command control by using
multifunction input terminals.
2: Communication (LOCAL/REMOT on)
Running commands are controlled by the upper
monitor through communication
P00.03
Max. output
frequency
This parameter is used to set the maximum
output frequency of the VFD. Pay attention to
this parameter because it is the foundation of the
frequency setting and the speed of acceleration
and deceleration.
Setting range:
–400.00Hz
50.00Hz
◎
P00.04
Upper limit of
running
frequency
The upper limit of the running frequency is the
upper limit of the output frequency of the VFD,
which is lower than or equal to the maximum
output frequency.
When the set frequency is higher than the upper
limit of the running frequency, the upper limit of
the running frequency is used for running.
Setting range:
(Max. output
frequency)
50.00Hz
◎
P00.05
Lower limit of
running
frequency
The lower limit of the running frequency is the
lower limit of the output frequency of the VFD.
When the set frequency is lower than the lower
limit of the running frequency, the lower limit of
the running frequency is used for running.
Note:
Max. output frequency ≥ Upper limit of
frequency ≥ Lower limit of frequency
Setting range: 0.00Hz
(Upper limit of
0.00Hz
◎