Goodrive18 series two-in-one VFD Function parameters and function terminal reuse
-31-
Function
code
Name
Description
Default
value
Modify
running frequency)
P00.06
Setting channel
of A frequency
command
Note:
A frequency and B frequency cannot use
the same frequency given method. The
frequency source can be set by
0: Keypad
Modify the value
(frequency set by
keypad) to modify the frequency by the keypad.
1: Reserved
2: Analog AI2 setting (corresponding terminal
AI2)
3: Analog AI3 setting (corresponding terminal
AI3)
Set the frequency by analog input terminals.
Goodrive18 series VFD provides 3 channels of
analog input terminal as the standard
configuration, of which AI2 can select voltage or
current (0
–10V/0–20mA) by jumper; while AI3 is
voltage input (-10V
–+10V).
Note:
When AI2 selects 0
–20mA input, the
corresponding voltage of 20mA is 10V.
100.0% of the analog input setting corresponds
to the maximum output frequency (
) in
forward direction and -100.0% corresponds to
the maximum output frequency (
) in
reverse direction.
4: Reserved
5: Simple PLC program
The VFD runs at simple PLC program mode
when
=5. Set P10 (simple
PLC and multi-step speed control) to select the
running frequency, running direction, ACC/DEC
time and the keeping time of corresponding
stage. See the function description of P10 for
detailed information.
6: Multi-step speed running
The VFD runs at multi-step speed mode when
=6. Set P05 to select the
0
○
P00.07
Setting channel
of B frequency
command
2
○