Goodrive200
inverters Basic operation instruction
145
Function
code
Name
Detailed instruction of parameters
Default
value
on model
P00.12
DEC time 1
0.0~3600.0s
Depend
on model
P02.02
Rated frequency of AM 1 0.01Hz~P00.03(the Max. frequency)
50.00
Hz
P02.04
Rated voltage of AM 1 0~1200V
380V
P04.00
Motor 1 V/F curve setting
0:Straight line V/F curve
;
applying to the
constant torque load
1:Multi-dots V/F curve
2:1.3
th
power low torque V/F curve
3:1.7
th
power low torque V/F curve
4:2.0th power low torque V/F curve
5:Customized V/F(V/F separation)
0
P04.01
Motor 1 torque boost
0.0%:(automatic)0.1%~10.0%
0.0%
P04.02
Motor 1 torque boost close
0.0%~50.0%
(the rated frequency of motor 1)
20.0%
P04.03
V/F frequency 1 of motor 1 0.00Hz~P04.05
0.00Hz
P04.04
V/F voltage 1 of motor 1
0.0%~110.0%
00.0%
P04.05
V/F frequency 2 of motor 1 P04.03~ P04.07
00.00Hz
P04.06
V/F voltage 2 of motor 1
0.0%~110.0%
00.0%
P04.07
V/F frequency 3 of motor 1 P04.05~ P02.02
00.00Hz
P04.08
V/F voltage 3 of motor 1
0.0%~110.0%
00.0%
P04.09
V/F slip compensation
gain of motor 1
0.0~200.0%
0.0%
P04.10
Motor 1 low frequency
vibration control factor
0~100
10
P04.11
Motor 1 high frequency
vibration control factor
0~100
10
P04.12
Motor 1 vibration control
threshold
0.00Hz~P00.03 (the Max. frequency)
30.00 Hz
P04.26
Energy-saving operation
0: No action
0
Summary of Contents for GD200-037G/045P-4
Page 1: ...Goodrive 200 Inverter ...
Page 44: ...Goodrive200 inverters Keypad operation procedure 43 Fig 5 5 Sketch map of state watching ...
Page 158: ...Goodrive200 inverters Basic operation instruction 157 ...
Page 208: ...Goodrive200 inverters Fault tracking 207 8 6 2 Motor vibration 8 6 3 Overvoltage ...
Page 209: ...Goodrive200 inverters Fault tracking 208 8 6 4 Undervoltage fault 8 6 5 Inverter overheating ...
Page 210: ...Goodrive200 inverters Fault tracking 209 8 6 6 Abnormal motor heat ...
Page 211: ...Goodrive200 inverters Fault tracking 210 8 6 7 Stall during the acceleration of the motor ...
Page 266: ...1 1 0 0 1 0 0 7 7 9 6 6 0 0 1 0 0 0 9 5 201701 V2 2 ...