Goodrive200
inverters Basic operation instruction
193
Function
code
Name
Detailed instruction of parameters
Default
value
P05.01~P05.09
Digital input function
selection
26:Traverse Pause (stop at the current
frequency)
27:Traverse reset (return to the center
frequency)
P08.15
Traverse range
0.0~100.0%
(relative to the setting frequency)
0.0%
P08.16
Sudden jumping
frequency range
0.0~50.0%
(relative to the traverse range)
0.0%
P08.17
Traverse boost time
0.1~3600.0s
5.0s
P08.18
Traverse declining
time
0.1~3600.0s
5.0s
7.17 Pulse counter
Goodrive200 series inverters support pulse counter which can input counting pulse through HDI
terminal. When the actual length is longer than or equal to the set length, the digital output terminal
can output length arrival pulse signal and the corresponding length will be cleared automatically.