Goodrive200 inverters Function codes
65
Function
code
Name
Detailed instruction of parameters
Default
value
Modify
coefficient
1
P03.11
Torque
setting
method
This parameter is used to enable the torque
control mode, and set the torque.
0:Torque control is invalid
1:Keypad setting torque(P03.12)
2:Analog AI1 setting torque
3:Analog AI2 setting torque
4:Analog AI3 setting torque
5:Pulse frequency HDI setting torque
6:Multi-step torque setting
7:MODBUS communication setting torque
8~10:Reserved
Note: Setting modes 2~10, 100% corresponds to
three times of the rated current of the motor.
0
○
P03.12
Keypad
setting
torque
Setting range: -300.0%~300.0%(rated current of
the motor)
50.0%
○
P03.13
Torque
reference
filter time
0.000~10.000s
0.010s
○
P03.14
Upper
frequency
of forward
rotation in
vector
control
0:Keypad
(P03.16 sets P03.14,P03.17 sets P03.15)
1: AI1
2: AI2
3: AI3
4:Pulse frequency HDI setting upper-limit
frequency
5:Multi-step setting upper-limit frequency
6:MODBUS communication setting upper-limit
0
○
P03.15
Upper
frequency
0
○
Summary of Contents for GD200-037G/045P-4
Page 1: ...Goodrive 200 Inverter ...
Page 44: ...Goodrive200 inverters Keypad operation procedure 43 Fig 5 5 Sketch map of state watching ...
Page 158: ...Goodrive200 inverters Basic operation instruction 157 ...
Page 208: ...Goodrive200 inverters Fault tracking 207 8 6 2 Motor vibration 8 6 3 Overvoltage ...
Page 209: ...Goodrive200 inverters Fault tracking 208 8 6 4 Undervoltage fault 8 6 5 Inverter overheating ...
Page 210: ...Goodrive200 inverters Fault tracking 209 8 6 6 Abnormal motor heat ...
Page 211: ...Goodrive200 inverters Fault tracking 210 8 6 7 Stall during the acceleration of the motor ...
Page 266: ...1 1 0 0 1 0 0 7 7 9 6 6 0 0 1 0 0 0 9 5 201701 V2 2 ...