Goodrive350 series high-performance multifunction VFD
Basic operation guidelines
-67-
Function
code
Name
Description
Default
value
P04.40
Enable/disable IF
mode for
asynchronous motor 1
0: Disabled
1: Enabled
0
P04.41
Current setting in IF
mode for
asynchronous motor 1
When IF control is adopted for asynchronous motor
1, this parameter is used to set the output current.
The value is a percentage in relative to the rated
current of the motor.
Setting range: 0.0
–200.0%
120.0%
P04.42
Proportional
coefficient in IF mode
for asynchronous
motor 1
When IF control is adopted for asynchronous motor
1, this parameter is used to set the proportional
coefficient of the output current closed-loop control.
Setting range: 0
–5000
650
P04.43
Integral coefficient in
IF mode for
asynchronous motor 1
When IF control is adopted for asynchronous motor
1, this parameter is used to set the integral
coefficient of the output current closed-loop control.
Setting range: 0
–5000
350
P04.44
Starting frequency
point for switching off
IF mode for
asynchronous motor 1
0.00Hz
–P04.50
10.00Hz
P04.45
Enable/disable IF
mode for
asynchronous motor 2
0: Disable
1: Enable
0
P04.46
Current setting in IF
mode for
asynchronous motor 2
When IF control is adopted for asynchronous motor
2, this parameter is used to set the output current.
The value is a percentage in relative to the rated
current of the motor.
Setting range: 0.0
–200.0%
120.0%
P04.47
Proportional
coefficient in IF mode
for asynchronous
motor 2
When IF control is adopted for asynchronous motor
2, this parameter is used to set the proportional
coefficient of the output current closed-loop control.
Setting range: 0
–5000
650
P04.48
Integral coefficient in
IF mode for
asynchronous motor 2
When IF control is adopted for asynchronous motor
2, this parameter is used to set the integral
coefficient of the output current closed-loop control.
Setting range: 0
–5000
350
P04.49
Starting frequency
point for switching off
IF mode for
0.00Hz
–P04.51
10.00Hz