Goodrive350 IP55 High-ingress Protection Series VFD
Function parameter list
-130-
Function
code
Name
Description
Default
value
Modify
P01.19
Action
selection
when the
running
frequency is
below lower
limit (lower
limit should be
larger than 0)
This function code is used to set the running state
of VFD when the set frequency is below lower limit
frequency.
Setting range: 0x00
–0x12
Ones place: Action selection
0: Run in lower limit of the frequency
1: Stop
2: Sleep
Tens place: Stop mode
0: Coast to stop
1: Decelerate to stop
The VFD sleeps or stops in a way set in the tens
place if the action selection is stop or sleep when
the set frequency is lower than the lower limit. The
VFD resumes the running state automatically
when the set frequency is above the lower limit
again and this situation lasts for the time set by
P01.20.
0x00
◎
P01.20
Wake-up-from
-sleep delay
This function code is used to set the sleep delay.
When the running frequency of VFD is below the
lower limit frequency, the VFD enters sleep state;
when the set frequency is above the lower limit
again and continues to be so after the time set by
elapses, the VFD will run automatically.
Sleep
Run
Set frequency curve:
Running frequency curve:
t1 < P01.20, the VFD does not run
t0=P01.34, sleep delay
Run
t2
t1
t0
Frequency lower
limit f0
Frequency f
Time t
Coast to
stop
t1+t2
≥
P01.20, the VFD runs
Setting range: 0.0
–3600.0s (valid when the ones
place of
is 2)
0.0s
○
P01.21
Restart after
power cut
This function code sets the automatic running of
the VFD at next power-on after power down.
0: Disabled restart
1: Enable restart, namely the VFD will run
automatically after the time set by
if the starting conditions are met.
0
○
P01.22
Waiting time of
restart after
power cut
This function code sets the waiting time before
automatically running at next power-on after power
down.
1.0s
○