Goodrive350 IP55 High-ingress Protection Series VFD
Function parameter list
-185-
Function
code
Name
Description
Default
value
Modify
P11.48
Fault severity
group 18
OtE1)
Group 16: Faults 71
–75 (OtE2, E-EIP, E-PAO,
E-AI1)
Group 17: Faults 75
–78 (E-AI2, E-AI3, Reserved,
Reserved)
Group 18: Faults 79
–82 (Reserved, Reserved,
Reserved, Reserved)
Group 19: Faults 83
–86 (Reserved, Reserved,
Reserved, Reserved)
Group 20: Faults 87
–90 (Reserved, Reserved,
Reserved, Reserved)
0x0000
○
P11.49
Fault severity
group 19
0x0000
○
P11.50
Fault severity
group 20
0x0000
○
P11.51
Action for fault
pre-alarm
0
–4
0: Run at the set frequency
1: Run at the output frequency at the time of fault
2: Run at the frequency upper limit
3: Run at the frequency lower limit
4: Run at the frequency reserved for exception
0
○
P11.52
Frequency
reserved for
exception
0.00
–630.00(Hz)
0.00Hz
○
P11.53
Fire mode
function
0
–2
0: Invalid
1: Fire mode 1
2: Fire mode 2
When P11.53=0, the fire mode is invalid, and the
normal running mode is used. In this case, the
VFD stops when encountering a fault.
When the fire mode function is valid, the VFD runs
at the speed specified by P11.54.
When fire mode 1 is selected, the VFD always
runs except when the VFD has been damaged.
When fire mode 2 is selected, the VFD always
runs, but the VFD stops when encountering OUT1,
OUT2, OUT3, OC1, OC2, OC3, OV1, OV2, OV3,
or SPO.
Note:
Terminal control must be used for a fire
mode.
When the fire mode has lasted 5 minutes, it is
reset, and no warranty of repair is processed.
0
◎
P11.54
Running
frequency in
fire mode
0.00Hz
–P00.03 (Max. output frequency)
50.00Hz
○
P11.55 Fire mode flag
0
–1
Note:
When the fire mode has lasted 5 minutes, it
is reset, and no warranty of repair is processed.
0
●