Goodrive350 IP55 High-ingress Protection Series VFD
Function parameter list
-236-
Function
code
Name
Description
Default
value
Modify
Note:
Temperature is displayed through P19.11.
To measure temperature, switch the output of
AO1 to current, and connect one end of the
temperature resistor to AI1 and AO1, and the
other end to GND.
P28.26
AI/AO detected
motor OH
protection
threshold
0.0
–200.0°C
Note: When the motor temperature exceeds the
threshold, the VFD releases the OT alarm.
110.0°C
○
P28.27
AI/AO detected
motor OH
pre-alarm
threshold
0.0
–200.0°C
Note:
When the motor temperature exceeds the
value, the DO terminal with function 48 (AI
detected motor OH pre-alarm) outputs a valid
signal.
90.0°C
○
P90
––Tension control in speed mode
Function
code
Name
Description
Default
value
Modify
P90.00
Tension control
mode
0: Invalid
1: Speed mode
2: Open-loop torque mode
3: Closed-loop torque mode
Note:
The value 0 indicates tension control is
invalid. Select a non-0 value to enable the
tension control function.
0
◎
P90.01
Winding/unwindi
ng mode
0: Winding
1: Unwinding
Note:
The motor forward rotation direction is the
winding direction. When using the tension
control mode, check whether the motor rotation
direction is correct in the winding mode; if not,
change the rotation direction by swapping two
phase wires of the motor. After the rotation
direction is corrected, the winding mode can be
switched to the unwinding mode by setting
P90.01 to 1 or changing the winding/unwiding
switchover terminals.
0
○
P90.02
Reel mechanical
transmission
rate
0.01
–600.00
=Motor rotation speed/Reel rotation speed=Reel
diameter/Motor shaft diameter
1.00
○
P90.03
Max. linear
speed
0.0
–6000.0 m/min
1000.0
m/min
○
P90.04
Input source of
linear speed
0: Keypad
1: AI1
2: AI2
3: AI3
0
◎