Goodrive350 IP55 High-ingress Protection Series VFD
Basic Operation Instructions
-60-
Function
code
Name
Description
Default
value
P04.47
Proportional coefficient in IF
mode for asynchronous
motor 2
When IF control is adopted for asynchronous
motor 2, this parameter is used to set the
proportional coefficient of the output current
closed-loop control.
Setting range: 0
–5000
650
P04.48
Integral coefficient in IF
mode for asynchronous
motor 2
When IF control is adopted for asynchronous
motor 2, this parameter is used to set the
integral coefficient of the output current
closed-loop control.
Setting range: 0
–5000
350
P04.49
Starting frequency point for
switching off IF mode for
asynchronous motor 2
0.00
–P04.51
10.00Hz
P04.50
End frequency point for
switching off IF mode for
asynchronous motor 1
P04.44
–P00.03
25.00Hz
P04.51
End frequency point for
switching off IF mode for
asynchronous motor 2
P04.49
–P00.03
25.00Hz
5.5.5 Torque control
The VFD supports torque control and speed control. Speed control mode aims to stabilize the
speed to keep the set speed consistent with the actual running speed, meanwhile, the max.
load-carrying capacity is restricted by torque limit. Torque control mode aims to stabilize the
torque to keep the set torque consistent with the actual output torque. Meanwhile, the output
frequency is restricted by upper/lower limit.