Goodrive350 IP55 High-ingress Protection Series VFD
Function parameter list
-124-
Function
code
Name
Description
Default
value
Modify
7: PID control
8: Modbus/Modbus TCP communication
9: PROFIBUS/CANopen/DeviceNet
communication
10: Ethernet communication
11: High speed pulse HDIB
12: Pulse train AB
13: EtherCAT/PROFINET/EtherNet IP
communication
14: Programmable card
15: Reserved
P00.08
Reference
object of B
frequency
command
0: Max. output frequency
1: A frequency command
0
○
P00.09
Combination
mode of
setting source
0: A
1: B
2: (A+B)
3: (A-B)
4: Max. (A, B)
5: Min. (A, B)
0
○
P00.10
Set frequency
via keypad
When A and B frequency commands are set by
keypad, the value is the initial digital set value of
the VFD frequency.
Setting range: 0.00 Hz
frequency)
50.00Hz
○
P00.11
Acceleration
time 1
Acceleration time is the time needed for
accelerating from 0Hz to max. output frequency
(
Deceleration time is the time needed from
decelerating from max. output frequency (
to 0Hz.
The Goodrive350 IP55 high-ingress protection
series VFD defines four groups of acceleration and
deceleration time, which can be selected via
multi-function digital input terminals (P05 group).
The acceleration/deceleration time of the VFD is
the first group by default.
Setting range of
P00.12
: 0.0
–3600.0s
Depend
on model
○
P00.12
Deceleration
time 1
Depend
on model
○
P00.13
Running
direction
0: Run in default direction
1: Run in reverse direction
2: Reverse running is prohibited
0
○