Goodrive350 IP55 High-ingress Protection Series VFD
Function parameter list
-126-
Function
code
Name
Description
Default
value
Modify
3: Static autotuning 2 (partial autotuning) ; when
current motor is motor 1, only
will be autotuned; when current motor is
motor 2, only
will be
autotuned.
4: Rotary autotuning 2, which is similar to rotary
autotuning 1 but is only applicable to
asynchronous motors.
5: Rotary autotuning 3 (partial autotuning), which
is only applicable to asynchronous motors.
P00.16
AVR function
0: Invalid
1: Valid during the whole process
Automatic voltage regulation function is used to
eliminate the impact on the output voltage of VFD
when bus voltage fluctuates.
1
○
P00.17
VFD model
0: G model
1: P model
P00.18
Function
parameter
restoration
0: No operation
1: Restore to default value
2: Clear fault records
3: Reserved
4: Reserved
5: Restore default values (for factory test mode)
6: Restore default values (including motor
parameters)
Note:
After the selected function operations are
done, this function code will be restored to 0
automatically. Restoration to default value will
clear the user password, so this function should be
used with caution. The option 5 can be used only
for factory testing.
0
◎
P01
––Start/stop control
Function
code
Name
Description
Default
value
Modify
P01.00
Running mode
of start
0: Direct start
1: Start after DC brake
2: Start after speed-tracking
0
◎
P01.01
Starting
frequency of
direct start
Starting frequency of direct startup is the initial
frequency when the VFD starts. See
time of starting frequency) for details.
Setting range: 0.00
–50.00Hz
0.50Hz
◎