Goodrive350 IP55 High-ingress Protection Series VFD
Function parameter list
-131-
Function
code
Name
Description
Default
value
Modify
Output frequency
Running
Power off
Power on
Running
t
t1
t2
t1=P01.22
t2=P01.23
Setting range: 0.0
–3600.0s (valid when
1)
P01.23
Start delay
This function code sets the delay of the VFD
’s
wake-up-from-sleep after running command is
given, the VFD will start to run and output after the
time set by
release.
Setting range: 0.0
–600.0s
0.0s
○
P01.24
Stop speed
delay
0.0
–600.0s
0.0s
○
P01.25
Open-loop
0Hz output
selection
0: No voltage output
1: With voltage output
2: Output as per DC brake current of stop
0
○
P01.26
Deceleration
time of
emergency-st
op
0.0
–60.0s
2.0s
○
P01.27
Time of
starting
section of
deceleration S
curve
0.0
–50.0s
0.1s
◎
P01.28
Time of ending
section of
deceleration S
curve
0.0
–50.0s
0.1s
◎
P01.29
Short-circuit
brake current
When the VFD starts in direct start mode
(
=0), set
enter short-circuit brake.
During stop, if the running frequency of VFD is
below the starting frequency of brake after stop
(
), set
short-circuit brake after stop, and then carry out
DC brake in the time set by
: 0.0
–150.0% (of the rated
VFD output current)
Setting range of
: 0.0
–50.0s
Setting range of
: 0.0
–50.0s
0.0%
○
P01.30
Hold time of
short-circuit
brake at
startup
0.00s
○
P01.31
Hold time of
short-circuit
brake at stop
0.00s
○
P01.32
Pre-exciting
time of jogging
0
–10.000s
0.000s
○