Goodrive350 IP55 High-ingress Protection Series VFD
Installation Guide
-20-
4.3 Standard wiring of main circuit
4.3.1 Wiring diagram of main circuit
Figure 4-7 Main circuit wiring diagram
037G/045P and below
045G/055P–110G
Brake resistor
Brake unit
Brake resistor
Input
reactor
Input
filter
Fuse
Input
reactor
Input
filter
3PH power
supply
380V(-15%)
50/60Hz
–
440V(+10%)
50/60Hz
R
S
T
R
S
T
U
V
W
PE
Output
reactor
Output
filter
M
(+) (-)
(+)
(-)
PB
Fuse
U
V
W
PE
Output
reactor
Output
filter
M
DC+
DC-
3PH power
supply
380V(-15%)
50/60Hz
–
440V(+10%)
50/60Hz
Note:
1. The fuse, DC reactor, brake unit, brake resistor, input reactor, input filter, output reactor and
output filter are optional parts. See Appendix D "Optional peripheral accessories" for details.
2. When connecting the brake resistor, take off the yellow warning sign marked with PB, (+)
and (-) on the terminal block before connecting the brake resistor wire, otherwise, poor
contact may occur.