6. Installation and use procedures
Contents
This section includes the following topics:
6.2 Install and configure LBK System Series
6.3 Validate the safety functions
6.1 Before installation
6.1.1 Materials required
l
Two tamper-proof screws (see "Side screw specifications" on page 89) to fasten the sensors to the floor or
machinery.
l
Cables to connect the control unit to the first sensor and the sensors to one another, see "CAN bus cables
recommended specifications" on page 88.
l
A data micro-USB cable or, only if the Ethernet port is available, an Ethernet cable to connect the control unit
to the computer.
l
A bus terminator (product code: 07000003) with resistance of 120 Ω for the last sensor of the CAN bus.
l
A screwdriver for tamper-proof screws ("Side screw specifications" on page 89) to be used with the Hex pin
security bit supplied in the control unit package.
l
If necessary, to protect the sensor and to prevent reflections from generating undesired alarms, one Metal
protector kit (product code: 90202ZAA) per sensor. See the instructions supplied with the kit for installation
instructions.
Note
: the Metal protector kit is particularly recommended if the sensor is installed on parts that are moving,
vibrating or that are near vibrating parts.
6.1.2 Operating system required
l
Microsoft Windows 7 or later
l
Apple OS X 10.10 or later
6.1.3 Install the Inxpect Safety application
Note
: if the installation fails, the dependencies needed by the application may be missing. Update your operating
system or contact our Technical Support team to receive assistance.
1. Download the application from the www.inxpect.com/industrial/tools website and install it on the computer.
2. With Microsoft Windows operating system, download and install from the same site also the driver for USB
connection.
3. Start the application.
4. Choose the connection mode (data micro-USB or Ethernet). If desired, select the update command to
upgrade the firmware version.
Note
: the default IP address for the Ethernet connection is 192.168.0.20. The computer and the control unit
must be connected to the same network.
5. Set a new admin password, memorize it and provide it only to people who are authorized to change the
configuration.
6. Select the device (LBK System Series).
7. Set the working frequency. If the system is installed in one of the countries with national restrictions, select
the restricted band, otherwise select the full band.
Note
: this setting does not have any effect on system performance or safety.
8. Set the number of sensors connected.
LBK System Series | Instruction manual v1.2 SET 2021| SAF-UM-LBKBus-en-v1.2 | © 2020-2021 Inxpect SpA