6. Installation and use procedures
6.1.4 Initiate LBK System Series
1. Calculate the position of the sensor (see "Sensor position" on page 52) and the depth of the dangerous area
(see "Dangerous area calculation" on page 54).
2. "Install the control unit" below.
3. Open the Inxpect Safety application.
4. Optional. "Synchronize the control units" below.
5. "Define the area to be monitored" below.
6. "Configure the inputs and outputs" below.
7. "Install sensors on the floor" on the next page or "Install the sensors on the machinery" on page 66.
8. "Connect the control unit to the sensors" on page 67.
Note
: connect the sensors to the control unit off-site if access to the connectors becomes difficult once they
are installed.
9. "Save and print the configuration" on page 68.
10. If available, "Set the control unit Ethernet parameters" on page 68
11. "Validate the safety functions" on page 68.
6.2 Install and configure LBK System Series
6.2.1 Install the control unit
WARNING! To prevent tampering, make sure the control unit is only accessible to authorized
personnel (e.g. key-locked electrical panel).
1. Mount the control unit on the DIN rail.
2. Make electrical connections, see "Terminal blocks and connector pin-outs" on page 89 and "Electrical
NOTICE
: if at least one input is connected, the SNS input "V+ (SNS)" and the GND input "V- (SNS)" must also
be connected.
NOTICE
: when powered, the system takes about 2 s to start. During that period the outputs and the diagnostic
functions are deactivated and the green sensor status LEDs of the connected sensors flash.
Note
: to correctly connect the digital inputs, see "Voltage and current limits for digital inputs" on page 90.
6.2.2 Synchronize the control units
If there are more than one ISC-B01 control unit in the area, to configure the system and to perform the electrical
connections, see "Enable the multi-control unit synchronization function" on page 48.
6.2.3 Define the area to be monitored
WARNING! LBK System Series is disabled during configuration. Prepare opportune safety measures
in the dangerous area protected by the system before configuring the system.
1. In the Inxpect Safety application, click
Configuration
.
2. Add the desired number of sensors in the plane.
3. Define the position and inclination of each sensor.
4. Define the angular coverage of the field of view for each sensor.
5. Define the selected safety working modes, the detection distance and the restart timeout for each detection
field of each sensor.
6.2.4 Configure the inputs and outputs
1. In the Inxpect Safety application, click
Settings
.
2. Click
Digital Input-Output
and define the input and output functions.
3. If the muting is managed, click
Muting
and assign the sensors to the groups according to the logic of the
digital inputs.
4. Click
APPLY CHANGES
to save the configuration.