6. Installation and use procedures
6.3.4 Validate the restart prevention function
Example 1
Starting conditions
l
Detection field dependency
:
Dependent mode
l
Machinery in safe conditions
l
Two detection fields configured (detection field 1 and detection field 2)
l
Both the safety outputs (detection signal 1 and detection signal 2) deactivated
Validation
procedure
1. Stand still in detection field 1.
2. Check that the system maintains both related safety outputs deactivated. See
"Validate the system with Inxpect Safety" below.
3. Stand still in detection field 2.
4. Check that the system maintains only the second safety output deactivated. See
"Validate the system with Inxpect Safety" below.
5. If the safety outputs do not remain deactivated, see "Troubleshooting validation" on
Specifications
l
Stop longer than the restart timeout (Inxpect Safety >
Configuration
).
l
Stop in several different points, with special attention to the areas in close proximity to
the sensor and any blind spots, see "Example of stopping points" below.
l
Stop standing as well as laid down.
Example 2
Starting conditions
l
Detection field dependency
:
Independent mode
l
Machinery in safe conditions
l
Two detection fields configured (detection field 1 and detection field 2)
l
Both the safety outputs (detection signal 1 and detection signal 2) deactivated
Validation
procedure
1. Stand still in detection field 1.
2. Check that the system maintains only the specific safety output deactivated. See
"Validate the system with Inxpect Safety" below.
3. Repeat step 1 and 2 for detection field 2.
4. If the safety outputs do not remain deactivated, see "Troubleshooting validation" on
6.3.5 Example of stopping points
Stopping points for 110° field of view
Stopping points for 50° field of view
6.3.6 Validate the system with Inxpect Safety
WARNING! When the validation function is active, the system response time is not guaranteed.
The Inxpect Safety application is helpful during the safety functions validation phase and allows the sensors'
actual field of view to be checked based on their installation position.
1. Click
Validation
: the validation starts automatically.
2. Move in the monitored area as indicated in "Validate the access detection function" on the previous page and