24
2.10 Power Cable
Please follow the local wiring regulations. Follow environmental conditions and
refer to IEC60950-1.
2.10.1 AC input and output maximum current and power cable configuration.
For standard model in 30U cabinet (Battery inside)
Model
30KVA 60KVA 90KVA
Current (A)
55
110
165
Power cable (mm
2
)
10
35
70
Fixation torque force (lb-in)
20
20
20
For standard model in 42U cabinet (Battery inside)
Model
30KVA 60KVA 90KVA 120KVA
Current (A)
55
110
165
220
Power cable (mm
2
)
10
35
70
95
Fixation torque force (lb-in)
20
20
20
20
For extended series in 30U & 42U cabinet
Model
30KVA 60KVA 90KVA 120KVA 150KVA
Current (A)
55
110
165
220
275
Power cable (mm
2
)
10
35
70
95
150
Fixation torque force (lb-in)
20
20
20
20
20
Model
180KVA 210KVA 240KVA 270KVA 300KVA
Current (A)
330
385
440
495
550
Power cable (mm2)
240
300
300
120*2
150*2
Fixation torque force (lb-in)
20
20
20
20
20
Notice:
Installer has to consider the max. current and wiring gauge when considering future
extension.
2.10.2 DC input maximum current and power cable configuration.
For standard series in 30U cabinet (Battery inside)
Model
30KVA 60KVA 90KVA
Current (A)
100
200
300
Power cable (mm
2
)
25
95
150
Fixation torque force (lb-in)
20
20
20
Warning:
1.
When Load is less than 30KVA, at least two layers of battery modules (8 modules) have to be
installed.
2.
When Load is between 30KVA and 60KVA, three layers of battery modules (12 modules) have
to be installed in total.
3.
When Load is larger than 60KVA, the external battery cabinet must be installed.
4.
The same type of battery has to be used, if the battery is in parallel application.