88
8. Specifications
The chapter states the specifications of UPS.
8.1
Conformity And Standards
The UPS has been designed to conform to the European and international standards listed in
Table 8-1
.
Table 8-1
: European and international standards
Item
Normative reference
Uninterruptible power systems (UPS) –Part 1:
General and safety requirements for UPS
IEC/EN62040-1
Electromagnetic compatibility (EMC) requirements
for UPS
IEC/EN62040-2
Method of specifying the performance and test
requirements of UPS
IEC/EN62040-3
Notes:
ESD
IEC/EN 61000-4-2 Level 3
RS
IEC/EN 61000-4-3 Level 3
EFT
IEC/EN 61000-4-4 Level 3
Surge
IEC/EN 61000-4-5 Level 3
CS
IEC/EN 61000-4-6 Level 3
Power-Frequency Magnetic field IEC/EN 61000-4-8 Level 3
Low Frequency Signals
IEC/EN 61000-2-2 Level 10V
Conduction
IEC/EN62040-2 Category C3
Radiation
IEC/EN62040-2 Category C3
8.2 Environmental Characteristics
Table 8-2:
Environmental characteristics
Item
Unit
Specifications
Noise within 1 m
dB
Max. 73
Altitude
m
≤1000, derate power by 1% per 100m between 1000m and
2000m
Relative humidity
% RH
0 ~ 95, non-condensing
Operating temperature
°C
0 ~ 40°C
(Output capacity will be derated when temperature is over
30°C. It will be derated to 90% at 35°C and 80% at 40°C.
Storage and transport
temperature for UPS
°C
-15 ~ 60
8.3 Mechanical Characteristics
Table 8-3
: Mechanical characteristics
30U
Model
30U-90HV
30U-120HV
30U-180HV
Rated power (kVA)
Unit
90
120
180
Dimensions, W x D x H
mm
600 x 1100 x 1475
Weight
kg
675
335
437.5
Color
N/A
Black
Protection degree, IEC (60529)
N/A
IP20 (front door and back door is open or closed)