  SF6 Leakmate Instrument User Manual V1.0 

  

 

 

Unrivalled Gas Detect

ion.

 

Page 4 of 9 

ionscience.com

 

Introduction  

The SF6 LEAKMATE is a highly sensitive, processor controlled SF

6

 leak detector for mobile use, 

based on the proven detection principle of Negative Corona Discharge. It is small, lightweight, and 
easy to operate even for untrained personnel. With its audible and visual alarm indications and 
adjustable sensitivity, it is optimally suited for not only finding but also pinpointing SF

6

 leaks down 

to approximately 1E-6 cc/s.  

Warnings  

In confined spaces, a severe SF

6

 leak can flood the room to a concentration where oxygen is 

deprived to a dangerously low level. Entering such confined spaces poses serious danger of 
asphyxiation. Always ventilate such rooms before entering.  

Do not operate the instrument with no sensor tip in place; there is risk of electric shock.  

Commissioning  

3.1. Battery Installation  

Hold the instrument with the probe facing downwards, and the front panel towards you. With a 

firm press by thumb, slide the battery compartment door towards the back of the instrument, and 
remove it.  

Batteries are inserted with the positive cap facing outwards, as indicated by the marking visible 

inside the battery compartment.  

  

3.2. Installing / Replacing the Sensor Tip  

WARNING: 

Do not power up the instrument when no sensor tip is in place. Doing so may pose 

hazard of electric shock.  

Make sure the instrument is powered down before removing the sensor tip.  

The sensor tip is installed by gently screwing it on hand-tight.   

Only use sensor tips that are specified for this instrument. Using any other type of sensor tips, 

even if they may mechanically fit, will result in compromised detection performance.  

 
 

 

 

Summary of Contents for SF6 LEAKMATE

Page 1: ...d Gas Detection ionscience com Distributed by Air Met Scientific Pty Ltd Work with Confidence Air Met Sales Service P 1800 000 744 F 1800 000 774 E sales airmet com au Air Met Rental P 1300 137 067 E...

Page 2: ...und Laborgera te EMV Anforderungen Gruppe 1 Klasse B Sto raussendung Electrical equipment for measurement control and laboratory use EMC requirements Group 1 Class B equipment emissions section only D...

Page 3: ...g 4 3 1 Battery Installation 4 3 2 Installing Replacing the Sensor Tip 4 Operation 5 4 1 Turn the detector on off 5 4 2 Recommended Leak Detection Procedures 5 4 2 1 Principle of detection 5 4 2 2 Pre...

Page 4: ...h rooms before entering Do not operate the instrument with no sensor tip in place there is risk of electric shock Commissioning 3 1 Battery Installation Hold the instrument with the probe facing downw...

Page 5: ...mination is effectively suppressed The RESET button is used to trigger zeroing manually should conditions change during detection 4 2 2 Precautions Be sure to ventilate any closed space before enterin...

Page 6: ...Sensor tip The sensor tip may get contaminated over time when a decay in sensitivity becomes apparent soak it in absolute alcohol for a few minutes then dry it carefully with compressed air Again nev...

Page 7: ...ed Clean as pointed out above The sensor tip is subject to aging and may be worn Use a new sensor tip The detector gives false alarms The ambient atmosphere s content of detectable substances may have...

Page 8: ...oltage Ionization Sensitivity approx 1E 6 mbar l s for SF6 Response Recovery Time approx 1s Audio Frequency keyed alarm sound Display 7 pos LED Bar tricolour Probe 355 mm long flexible Self Diagnostic...

Page 9: ...x 49 2104 144825 Web www ism d de Email info ism d de Italian Office ION Science Italia Via delle Querce 1 g 40011 Anzola dell Emilia Bologna ITALY Tel 39 051 0561850 Fax 39 051 0561851 Web www ionsci...

Reviews: