Use the table below to solve minor problems.
Problems
6 LED
LCD
Solutions
panel
panel
BUS overvoltage
0000
0
~ 4
If the problem persists after rebooting,
please contact your supplier.
BUS under voltage
0001
5
~ 9
If the problem persists after rebooting,
please contact your supplier.
UPS output
0101
25
~ 29
If the problem persists after rebooting,
overvoltage
please contact your supplier.
UPS under voltage
0110
30
~ 34
If the problem persists after rebooting,
please contact your supplier.
UPS
1000
40
~ 44
Check if the air vents is blocked and
over-temperature
the fan is working properly.
UPS output short-
Check the load type, whether the load
1001
45
~ 49
is seriously overloaded, and whether
circuit
the load is short-circuited.
UPS output
1010
50
~ 54
Check the load and use it after
overload
reducing the load.
UPS output
Check the load type, whether the load
1011
55
~ 59
is seriously overloaded, and whether
overcurrent
the load is short-circuited.
Auxiliary power
supply
1100
60
~ 64
If the problem persists after rebooting,
disconnection
please contact your supplier.
failure
Battery overvoltage
1101
65
~ 69
Check if the battery is damaged and
the battery voltage is normal or not.
Relay fault
1110
70
~ 74
If the problem persists after rebooting,
please contact your supplier.