1.07.2020
www.ips-ups.eu
LiftUPS-manual-EN-R1
2 Specifications
Capacity
1000 VA / 600 W
1500 VA / 900 W
INPUT
Rated voltage
220 V / 230 V / 240 Vac (selectable)
Voltage range
220 V / 230 V / 240 Vac,
-
22% ~ + 26%, ± 5 Vac
Rated frequency
50 Hz / 60 Hz (selectable)
Frequency range
± 10% (default), ± 5% ~ 15% (selectable)
OUTPUT
Power factor
0.6
Battery mode: 220 V / 230 V / 240 Vac ± 10%
Output voltage
(selectable)
Mains power mode: synchronized with utility power
Output waveform
Battery mode: square wave;
Mains power mode: synchronized with utility power
Inversion efficiency
Max. > 87%
IT equipment
Yes
Half-wave load
≤ 50% (rated load)
Inductive load
No
BATTERIES
Rated voltage
60 Vdc
Battery capacity
12 V × 5, 4 ~ 9 Ah
Charging current
≤ 1 A
Equalizing charge
Single battery 14.2 Vdc (default),
voltage
13.6 ~ 15.0 Vdc (selectable)
Floating charge voltage
Single battery 13.6 Vdc
Low voltage alarm
Single battery 10.8 Vdc (default),
9.6 ~ 13.0 Vdc (selectable)
~ 2 ~