1.07.2020
www.ips-ups.eu
LiftUPS-manual-EN-R1
Low voltage shutdown
Single battery 10.2 Vdc (default),
9.6 ~ 12.0 Vdc (selectable)
Overvoltage protection
75 ± 2 Vdc
Overvoltage restored
68 ± 2 Vdc
SYSTEM
Transfer time
≤ 8 ms (typical) , ≤ 15 ms (max.)
Battery inversion time
1 min ~ 15 min (selectable)
Overload, short-circuit (battery mode),
Protections
over-temperature, output over/under-voltage,
excessive low battery
Overload times
> 110% for 120 s
,
> 125% for 60 s
,
> 150% for 10 s
,
(Mains mode)
> 200% for 1 s
Overload times
> 110% for 60 s, > 125% for 5 s, > 150% for 1 s
(Battery mode)
Communication
No
interface
Panel display
6 LED
3 LED
LCD
OTHERS
Operating temperature
0~45
℃
Operating humidity
0 ~ 95% (no-condensing)
Altitude
≤ 1000 m (Above 1000 m, derating 1% for each
additional 100 m)
IP rating
IP20
Cooling
Forced-air cooling
Noise
< 45 dB
Dimensions (mm)
205x146x70
Weight (kg)
1.50
1.50
1.52
Packaged weight (kg)
1.66
1.66
1.68
Note: "Selectable" can be customized according to customer requirements.
~ 3 ~