RACK TOWER ONLINE UPS
4.011.2017
RTS-ON-user-manual_ENG-R1
28
Turn on
Overload
Turn off
Battery inspection
Standby or Shutdown
Repeat
AC
Display screen repeat key
DC
Battery
Appendix 3: Specification Sheet (1-3KVA)
Rated Capacity
1KVA
1.5KVA
2KVA
3KVA
Input
Rated input voltage
220V or 120V
Rated input frequency
50Hz/60Hz auto-adaptive
Input voltage range
(the type of 220V)
(
11
5
~
295)
±5VAC (half load)
(
14
5
~
295)
±5VAC(full load)
Input voltage range
(the type of 120V)
(
5
5
~
1
45)
±5VAC(60% LOAD)
; (
6
5
~
1
45)
±5VAC(70% LOAD)
(
7
5
~
1
45)
±5VAC(80% LOAD)
; (
8
5
~
1
45)
±5VAC(100% LOAD)
Input frequency range
45-55Hz+/-0.5% 50Hz
type
55-65Hz+/-0.5% 60Hz
type
Input current
220V
8A max
12A max
15A max
23A max
120V
14A max
21A max
27A max
40A max
PFC
≥0.98
THDI
﹤
6%
Bypass voltage
range
220V
Rated output voltage -34V
~
Rated output v32V
120V
(
9
5~
1
35)
±5VAC
Output
Output voltage 220V
208VAC /220VAC/230VAC/240VAC Setting available via LCD