The Motor Diagnostics option is an extraordinary feature that can allow precise adjustment of the motor
maximum output force. When M1 or M2 diagnostics are turned on, upon exiting the menus, the display will
reflect the motor amperage high and voltage low in real time when the motor is running. At the end of the
cycle, the highest amperage and lowest voltage that was last detected will be displayed. By using this
feature, proper adjustment to the open and close force settings can be obtained. Be sure to turn the
diagnostic features off when not required
)
Motor Drive Menu
•
Number of Operators in System = 1 or 2
•
Operator 1 ‘IQ’ = IQ Gate(default) or Standard (the Standard option does not require the feedback from
an encoder from the motor)
•
M-1 Open Force = user selectable amperage level from 00.1 to 16.0
Default=10.0 amps
•
M-1 Close Force = user selectable amperage level from 00.1 to 16.0
Default=10.0 amps
•
Force Delay=
0.5
(
recommended
) this is the selectable time from .5 seconds up to 2 seconds in which
the amperage may be reached or exceeded before the gate reverses due to a motor open or close force
alarm
•
M-1 Max Speed = user selectable maximum motor speed from 10% to 100%
•
M-1 Min Speed = user selectable minimum motor speed from 10% to 90%
•
M-1 Open Delay = sets the desired open delay from 0.0 seconds to 5.0 seconds
•
M-1 Close Delay = sets the desired close delay from 0.0 seconds to 5.0 seconds
•
M-1 Acceleration Step Size = sets the rate of motor acceleration- the higher the rate, the faster the ramp
up to the maximum set speed
•
M-1 Deceleration Step Size = sets the rate of motor deceleration- the higher the rate, the faster the ramp
down to the minimum set speed
•
Operator 2 ‘IQ’ = IQ Gate or Standard
All M-2 options are the same as M-1
Exit the sub-menu
IQ Gate Learning – Enter if Applicable
(This menu is only used if “learning” IQ Gate Operators. This is the menu that will allow you to set the
desired closed limit as well as the location of the soft stop in a percentage value. To LEARN an IQ Gate style
gate operator, please refer to the “Quick Start Guide” section of this manual.)
•
Enter for Motor 1 Learning Mode
o
Use ‘Radio’ to learn Close Count
o
I-M-1 Close limit is _ _ _ _ counts
o
I-M-1 Open Slow Down at _ _% (this is the percent of gate travel that the soft stop would begin)
o
I-M-1 Close Slow Down at _ _% (this is the percent of gate travel that the soft stop would begin)
•
Enter for Motor 2 Learning Mode
o
Use ‘Radio’ to learn Close Count
o
I-M-2 Close limit is _ _ _ _ counts
o
I-M-2 Open Slow Down at _ _% (this is the percent of gate travel that the soft stop would begin)
o
I-M-2 Close Slow Down at _ _% (this is the percent of gate travel that the soft stop would begin)
•
Encoding Failure = Alarm and Stop or Alarm and Reverse
Upon encountering an Encoder err, the gate can be programmed to Stop and activate the Alarm relay, or
Reverse to an open or shut-down position and activate the Alarm relay.
Exit the sub-menu